Creating new alarms - Metasys - LIT-12013352 - M4-SNE10500-0 - M4-SNE10501-0 - M4-SNE11000-0 - M4-SNE11001-0 - M4-SNE110L0-0 - M4-SNE110L1-0 - M4-SNE22000-0 - M4-SNE22001-0 - Supervisory Device - SNE10 Network Engine - SNE11 Network Engine - SNE22 Network Engine - SNE Supervisory Network Engine - 12.0

SNE Commissioning Guide

Brand
Metasys
Product name
SNE10 Network Engine
SNE11 Network Engine
SNE22 Network Engine
SNE Supervisory Network Engine
Document type
Commissioning Guide
Document number
LIT-12013352
Version
12.0
Revision date
2022-12-12
Product status
Active
Language
English

About this task

You can create new alarms for the SNE or any of the supported field devices on the field trunks attached to the SNE.

Procedure

  1. Select and drag the required SNE or field device object from the Navigation panel into the Display panel. The SNE or field device object Focus screen opens.
  2. Select the Alarm tab and the device’s Alarm screen opens. Click New and the Insert Alarm Wizard opens (Figure 1).
    Figure 1. Insert Alarm Wizard

  3. Select the device Attribute for which you want to create an alarm.
  4. Follow the Wizard instructions and create or edit the values for the Attribute for which you want to create an alarm.
  5. Click Save when you have finished creating the required alarm parameters for the device Attribute.