Moving security database and clearing it from demoted Site Director prior to Release 6.0 - Metasys - LIT-12013352 - M4-SNE110L0-0 - M4-SNE10501-0 - M4-SNE22001-0 - M4-SNE10500-0 - M4-SNE11001-0 - M4-SNE110L1-0 - M4-SNE11000-0 - M4-SNE22000-0 - Supervisory Device - SNE Supervisory Network Engine - SNE22 Network Engine - SNE11 Network Engine - SNE10 Network Engine - 12.0

SNE Commissioning Guide

Product
Network Engines > Network Control Engines > SNE22 Network Engine
Network Engines > Network Control Engines > SNE11 Network Engine
Document type
Commissioning Guide
Document number
LIT-12013352
Version
12.0
Revision date
2022-12-12
Product status
Active

Procedure

  1. Create a backup of the Security database of the demoted device, but only if you are using the same set of users on the new or existing Site Director.
  2. Create a backup of the Security database from one of the devices (Metasys Server or network engine) on the site that has never been a Site Director and has never had a Site Director’s Security database restored to it (in other words, has a clean Security database with only the default user accounts).
  3. Restore the clean copy of the Security database that you created in Step 2 to the device that was demoted from the Site Director.
  4. If you are using the Security database of the demoted device on the new Site Director, restore the Security database that you backed up in Step 1 to the new or existing Site Director.
  5. Create a backup of the Security database from the device that was demoted and restored with a clean database in Step 3.

    This step ensures that the device Security database in the SCT matches the clean Security you restored to the device in Step 3.