Replacing a Self-Signed Certificate - Metasys - LIT-12011964 - Software Application - System Configuration Tool - 16.0

SCT: System Configuration Tool Help

Brand
Metasys
Product name
System Configuration Tool
Document type
User Guide
Document number
LIT-12011964
Version
16.0
Revision date
2023-10-02
Language
English

About this task

Follow these steps to replace an existing certificate with a new self-signed certificate for a network engine in the archive database. This procedure is useful if you need to replace an expired or compromised trusted certificate with a self-signed certificate.

Procedure

  1. Open the archive database.
  2. On the Tools menu, select Certificate Management. The Certificate Management screen appears.
  3. Click the Devices tab. A table of all devices with certificates appears.
    Figure 1. Devices Tab in Certificate Management

  4. Select the device and click Replace Self-sign.