Modifying Controller Templates with the Rapid Archive Field Controller wizard - Metasys - LIT-12011964 - Software Application - System Configuration Tool - 16.0

SCT: System Configuration Tool Help

Brand
Metasys
Product name
System Configuration Tool
Document type
User Guide
Document number
LIT-12011964
Version
16.0
Revision date
2023-10-02
Language
English

Procedure

  1. Open the Rapid Archive Field Controller wizard.
  2. Click Edit.
  3. Select the Create Points check box and clear the Create Metasys UI Spaces and Equipment check box.
  4. Navigate to the controller you want to modify.
  5. In the Controller Template column, click the drop-down arrow, and do one of the following:
    • Select a different controller template. This selection removes the existing controller template and deletes associated points, including any extensions, and recreates the points indicated by the new template.
    • Select the duplicate controller template of the current template selection from drop-down menu. For example, if * vavsd is currently listed, select vavsd (Figure 1). This selection deletes all of the existing points under the controller and recreates them based on the current state of the selected controller template.
      Figure 1. Duplicate Controller Template Selection
  6. Click Save.