An Equipment object is created through the option and through equipment discovery when creating Equipment Definitions. Equipment objects are listed in the Equipment tree in SCT. This object contains attributes common to many Metasys system objects. These common attributes are described in the Common Object Attributes section.
|
Attribute Name |
Data Type |
Notes |
Initial Value |
Values/Options/Ranges |
|---|---|---|---|---|
|
Name |
Text |
C |
Maximum length of 400 characters |
|
|
Description |
Text |
C |
Maximum length of 64 characters |
|
| Object Type | One type from a set | C | Equipment | Undefined |
|
Authorization Category |
One type from a set |
C |
HVAC |
HVAC, Fire, Security, Services, Administrative, General Lighting, Refrigeration, Critical Environment, Air Quality, Power, Energy, System Custom 1–150 |
|
Served By |
List of |
C |
Listof[0] |
|
|
Definition Link |
Reference |
C |
Blank or Object Name and Reference of Equipment Definition |
Blank or Object Name and Reference of Equipment Definition |
|
Graphic |
Object Reference |
C W |
Blank or Object Name and Reference |
|
| Graphic Alias | Reference Strings (fully qualified references) |
Maximum 256 characters |