Upgrading from SCT Release 11.1 or later to Release 13.2 software - Metasys - LIT-12012067 - Configuration software - SCT System Configuration Tool - 13.2

SCT Installation and Upgrade Instructions

Product
Building Automation Systems > Configuration and Programming Tools > SCT System Configuration Tool
Document number
LIT-12012067
Version
13.2
Revision date
2019-10-14

About this task

Note: If you have SCT Release 11.0 or earlier installed on your computer you must uninstall the software before you can upgrade to the latest release.

Procedure

  1. Obtain the SCT installation file from the License Portal.
  2. Run MetasysSystemConfigurationTool_13.2.exe. The Metasys System Configuration Tool Setup window appears.
    Figure 1. Metasys System Configuration Tool setup window
  3. Click Upgrade. The SQL Server Credential window appears.
    Figure 2. SQL Server credential window
  4. Log in to SQL Server in one of two ways:
    • To log in with Windows Credentials, keep the Use Windows Credentials checkbox selected.
    • To log in using SQL Server authentication, deselect the Use Windows Credentials check box and enter the SA user username and password.
  5. Click Upgrade. The upgrade process begins. If you are prompted to restart the computer, click Restart Now. The upgrade is complete.
    Figure 3. Software upgrade complete window