Dynamically Creatable: Yes
Dynamically Deletable: Yes
|
Property Name |
Required |
Optional |
Proprietary |
Property ID |
Data Type |
Writable |
Range |
|---|---|---|---|---|---|---|---|
|
BUFFER_SIZE |
X |
126 |
X 1 |
2-5000 |
|||
|
ENABLE |
X |
133 |
X |
||||
|
LOGGING_TYPE |
X |
197 |
X1 |
||||
|
OBJECT_NAME |
X |
77 |
X |
||||
|
RECORD_COUNT |
X |
371 |
X |
||||
|
STOP_WHEN_FULL |
X |
144 |
X |
||||
|
ACKED_TRANSITION 2 |
X |
0 |
|||||
|
ALIGN_INTERVALS |
X |
193 |
|||||
|
CLIENT_COV_INCREMENT |
X |
127 |
X |
||||
|
COV_RESUBSC_INTERVAL |
X |
128 |
X |
Any value > 0 |
|||
|
DESCRIPTION |
X |
28 |
X |
64 characters max |
|||
| EVENT_DETECTION_ENABLE2 | X | 353 | |||||
|
EVENT_ENABLE2 |
X |
35 |
X 3 |
||||
|
EVENT_MESSAGE_TEXTS2 |
X |
351 |
X3 |
||||
| EVENT_MESSAGE_TEXTS_ CONFIG2 | X | 352 | X3 | 256 characters max | |||
|
EVENT_TIME_STAMPS2 |
X |
130 |
|||||
|
INPUT_REFERENCE 4 |
X |
132 |
X1 |
||||
|
INTERVAL_OFFSET |
X |
195 |
X |
||||
|
LAST_NOTIFY_TIME |
X |
173 |
|||||
|
LOG_INTERVAL 5 |
X |
134 |
X |
||||
|
NOTIFICATION_CLASS2 |
X |
17 |
X3 |
1–4,194,303 |
|||
|
NOTIFY_THRESHOLD2 |
X |
137 |
X3 |
||||
|
NOTIFY_TYPE2 |
X |
72 |
X3 |
||||
|
PROFILE_NAME |
X |
168 |
|||||
|
RECORDS_SINCE_NOTIFY2 |
X |
140 |
|||||
|
RELIABILITY |
X |
103 |
X1 |
||||
|
START_TIME |
X |
142 |
X |
||||
|
STOP_TIME |
X |
143 |
X |
||||
|
TRIGGER |
X |
205 |
X |
||||
|
ALARM_STATE |
X |
1006 |
Enumerated |
||||
|
BACNET_EXPOSED |
X |
3807 |
Boolean |
||||
|
BUFFER_STATE |
X |
2565 |
Enumerated |
||||
|
ENABLED |
X |
673 |
Boolean |
X |
|||
|
EXECUTION_PRIORITY |
X |
2197 |
Enumerated |
X |
0–3 |
||
|
INPUT_REF |
X |
545 |
Complex |
X1 |
|||
|
INSTANCE_NUMBER |
X |
32589 |
Unsigned |
||||
|
ITEM_REFERENCE |
X |
32527 |
Character String |
||||
|
MAPPED_NAME |
X |
2564 |
String |
||||
|
NEXT_TRANSFER_COUNT |
X |
2553 |
Unsigned |
||||
|
NOTIFICATION_OBJ_REF |
X |
4304 |
Object Reference |
X1 |
|||
|
OBJECT_CATEGORY |
X |
908 |
Enumerated |
X |
|||
|
REMOTE_DESCRIPTION 6 |
X |
32519 |
Character String |
X |
|||
|
REMOTE_DEVICE_ADDRESS6 |
X |
538 |
Complex |
||||
|
REMOTE_RELIABILITY |
X |
32518 |
Enumerated |
||||
|
RESPOSITORY_ENABLED |
X |
2549 |
Boolean |
X |
|||
|
ROUTE_TRIGGER |
X |
2552 |
Boolean |
X |
|||
|
SAMPLE_INTERVAL5 |
X |
2566 |
Unsigned |
X |
|||
|
STATUS |
X |
512 |
Enumerated |
||||
|
TRANSFER_SETPOINT |
X |
2550 |
Unsigned |
X |
1–5,000 |
||
|
USER_NAME |
X |
2390 |
Character String |
X |