Dynamically Creatable: Yes
Dynamically Deletable: Yes
|
Property Name |
Required |
Optional |
Proprietary |
Property ID |
Data Type |
Writable |
Range |
|---|---|---|---|---|---|---|---|
|
EFFECTIVE_PERIOD |
X |
32 |
X |
||||
|
LIST_OF_PROP_REFS |
X |
54 |
|||||
|
OBJECT_NAME |
X |
77 |
X |
||||
|
OUT_OF_SERVICE |
X |
81 |
X |
||||
|
PRESENT_VALUE |
X |
85 |
X 1 |
||||
|
PRIORITY_FOR_WRITING |
X |
88 |
X |
||||
|
SCHEDULE_DEFAULT |
X |
174 |
X |
||||
|
DESCRIPTION |
X |
28 |
X |
64 characters max |
|||
|
EXCEPTION_SCHEDULE |
X |
38 |
X 3 |
||||
|
PROFILE_NAME 3 |
X |
168 |
|||||
|
WEEKLY_SCHEDULE |
X |
123 |
X |
||||
|
ALARM_STATE |
X |
1006 |
Enumerated |
||||
|
BACNET_EXPOSED |
X |
3807 |
Boolean |
X |
|||
|
COV_COUNT3 |
X |
839 |
Byte |
||||
|
DEVICE_MAC_ADDRESS3 |
X |
3629 |
Byte |
||||
|
DEVICE_TIME ZONE |
X |
1403 |
Enumerated |
||||
|
DISPLAY_UNITS3 |
X |
2207 |
Enumerated |
X |
|||
|
ENABLE_OBJECT_TYPE_ VALIDATION3 |
X |
3983 |
Boolean |
X |
|||
|
ENABLED |
X |
673 |
Boolean |
X |
|||
|
EXCEPTION_SCHEDULE3 |
X |
38 |
List |
||||
|
EXECUTION_PRIORITY |
X |
2197 |
Enumerated |
X |
0–3 |
||
|
IN_TEST3 |
X |
3368 |
Boolean |
||||
|
INSTANCE_NUMBER |
X |
32589 |
Unsigned |
||||
|
ITEM_REFERENCE |
X |
32527 |
Character String |
||||
|
JCI_EXCEPTION_SCHEDULE |
X |
2573 |
List |
X |
|||
|
JCI_LIST_OF_PROPERTY_REF |
X |
2574 |
List |
X |
|||
|
MAPPED_NAME3 |
X |
2564 |
String |
||||
|
OBJECT_CATEGORY |
X |
908 |
Enumerated |
X |
|||
|
OFFLINE3 |
X |
913 |
Boolean |
||||
|
PERFORM_INDEX3 |
X |
965 |
Unsigned |
||||
|
REMOTE_DESCRIPTION3 |
X |
32519 |
Character String |
X |
|||
|
REMOTE_DEVICE_ADDRESS3 |
538 |
Complex |
|||||
|
SCHEDULE_DATA_TYPE |
X |
951 |
Enumerated |
X |
|||
|
SCHEDULE_TYPE |
X |
950 |
Enumerated |
X |
|||
|
SICS_BEHAVIOR3 |
X |
4349 |
Boolean |
X |
|||
|
START_TIME_SCHEDULE_ VALUE3 |
X |
1728 |
Enumerated |
||||
|
STATES TEXT3 |
X |
931 |
Enumerated |
X |
|||
|
STATUS |
X |
512 |
Enumerated |
||||
|
STOP_TIME_SCHEDULE_VALUE |
X |
1729 |
Enumerated |
||||
|
TODAYS_SCHEDULE3 |
X |
4198 |
List |
||||
|
TRUNK_NUMBER3 |
X |
549 |
Byte |
||||
|
USER_NAME |
X |
2390 |
Character String |
X |
400 characters max |