Program - Metasys - LIT-12013310 - Server - Open Application Server - 13.0

Open Application Server (OAS) Protocol Implementation Conformance Statement

Product
Building Automation Systems > Application Servers > Open Application Server
Document number
LIT-12013310
Version
13.0
Revision date
2023-11-08
Product status
Active

Dynamically Creatable: No

Dynamically Deletable: No

Table 1. Program

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

OBJECT_NAME

X

   

77

 

X

 

PROGRAM_CHANGE

X

   

90

 

X

 

DESCRIPTION

 

X

 

28

 

X

64 characters max

DESCRIPTION_OF_HALT

 

X

 

29

     

INSTANCE_OF

 

X

 

48

     

PROGRAM_LOCATION

 

X

 

91

 

X 1

 

PROFILE_NAME

 

X

 

168

     

REASON_FOR_HALT

 

X

 

100

     

RELIABILITY

 

X

 

103

 

X1

 

ACS_VERSION 2

   

X

4128

Byte

X1

 

ALARM_STATE

   

X

1006

Enumerated

   

APPLICATION_STATE2

   

X

11037

Enumerated

X1

 

ARCHIVE_NAME2

   

X

32521

String

X1

 

ATTRIBUTE_INFO

   

X

2554

List

X

 

AUTHORIZATION_CATEGORY

   

X

908

Enumerated

X

0–249

DMCS_VERSION2

   

X

4129

Byte

X1

 

ENABLED

   

X

673

Boolean

X

 

EXECUTION_PRIORITY

   

X

2197

Enumerated

X

 

FILE_NAME2

   

X

902

Complex

X1

 

GRAPHIC

   

X

32581

Object Reference

X

 

GRAPHIC_ALIAS

   

X

32623

String

X

 

LOGIC_SEQUENCE

   

X

2529

List

X

 

INPUT_1

   

X

50083

Numeric

X

 

INPUT_2

   

X

50084

Numeric

X

 

INPUT_3

   

X

2362

Numeric

X

 

INPUT_4

   

X

2363

Numeric

X

 

INPUT_5

   

X

2364

Numeric

X

 

INPUT_6

   

X

2365

Numeric

X

 

INPUT_7

   

X

2366

Numeric

X

 

INPUT_8

   

X

2367

Numeric

X

 

INPUT_9

   

X

2368

Numeric

X

 

INPUT_10

   

X

2369

Numeric

X

 

INPUT_11

   

X

2370

Numeric

X

 

INPUT_12

   

X

2371

Numeric

X

 

INPUT_13

   

X

2372

Numeric

X

 

INPUT_14

   

X

2373

Numeric

X

 

INPUT_15

   

X

2374

Numeric

X

 

INPUT_16

   

X

2375

Numeric

X

 

INPUT_17

   

X

2376

Numeric

X

 

INPUT_18

   

X

2377

Numeric

X

 

INPUT_19

   

X

2378

Numeric

X

 

INPUT_20

   

X

2379

Numeric

X

 

INPUT_21

   

X

2500

Numeric

X

 

INPUT_22

   

X

2501

Numeric

X

 

INPUT_23

   

X

2502

Numeric

X

 

INPUT_24

   

X

2503

Numeric

X

 

MAPPED_NAME

   

X

2564

String

   

INSTANCE_NAME

   

X

32589

Unsigned

   

ITEM_REFERENCE

   

X

32527

String

   

LAST_MODIFICATION_DATE

   

X

6096

Complex

X

 

LOGIC_SEQUENCE

   

X

2529

List

X

 

OBJECT_CATEGORY

   

X

908

Enumerated

X

 

OBJECT_COUNT

   

X

844

Unsigned

   

OUTPUT_1

   

X

2505

Numeric

   

OUTPUT_2

   

X

2506

Numeric

   

OUTPUT_3

   

X

2507

Numeric

   

OUTPUT_4

   

X

2508

Numeric

   

OUTPUT_5

   

X

2509

Numeric

   

OUTPUT_6

   

X

2510

Numeric

   

OUTPUT_7

   

X

2511

Numeric

   

OUTPUT_8

   

X

2512

Numeric

   

OUTPUT_9

   

X

2513

Numeric

   

OUTPUT_10

   

X

2514

Numeric

   

OUTPUT_11

   

X

2515

Numeric

   

OUTPUT_12

   

X

2516

Numeric

   

OUTPUT_13

   

X

2517

Numeric

   

OUTPUT_14

   

X

2518

Numeric

   

OUTPUT_15

   

X

2519

Numeric

   

OUTPUT_16

   

X

2520

Numeric

   

OUTPUT_17

   

X

2521

Numeric

   

OUTPUT_18

   

X

2522

Numeric

   

OUTPUT_19

   

X

2523

Numeric

   

OUTPUT_20

   

X

2524

Numeric

   

OUTPUT_21

   

X

2525

Numeric

   

OUTPUT_22

   

X

2526

Numeric

   

OUTPUT_23

   

X

2527

Numeric

   

OUTPUT_24

   

X

2528

Numeric

   

PRIORITY

   

X

86

Enumerated

   

REMOTE_DESCRIPTION

   

X

32519

String

X

 

REMOTE_DEVICE_ADDRESS

   

X

538

String

   

STARTUP_TIME

   

X

63947

Unsigned

X

 

STATUS

   

X

512

Enumerated

   

SYSTEM_NAME

   

X

910

String

   

SYSTEM_OF_UNITS_SELECTION

   

X

6057

Enumerated

   

TEST_MODE

   

X

3620

Enumerated

   

USER_NAME

   

X

2390

String

   
1 Not writable in all instances.
2 Not present in all instances.