Dynamically Creatable: Yes
Dynamically Deletable: Yes
|
Property Name |
Required |
Optional |
Proprietary |
Property ID |
Data Type |
Writable |
Range |
|---|---|---|---|---|---|---|---|
|
ACK_REQUIRED |
X |
1 |
X |
||||
|
OBJECT_NAME |
X |
77 |
X |
||||
|
PRIORITY |
X |
86 |
X |
||||
|
RECIPIENT_LIST |
X |
102 |
X |
||||
|
DESCRIPTION |
X |
28 |
X |
64 characters max |
|||
|
ALARM_STATE |
X |
1006 |
Enumerated |
||||
|
AUTHORIZATION_CATEGORY |
X |
908 |
Enumerated |
X |
0–249 |
||
|
ENABLED |
X |
673 |
Boolean |
X |
|||
|
EXECUTION_PRIORITY |
X |
2197 |
Enumerated |
X |
0–3 |
||
|
ITEM_REFERENCE |
X |
32527 |
Character String |
||||
| MAPPED_NAME 1 |
X |
2564 |
String |
||||
|
OBJECT_CATEGORY |
X |
908 |
Enumerated |
X |
|||
|
REMOTE_DESCRIPTION1 |
X |
32519 |
Character String |
X |
|||
|
REMOTE_DEVICE_ADDRESS1 |
X |
538 |
Complex |
||||
|
ROUTE_TO_METASYS |
X |
32580 |
Boolean |
X |
|||
|
SEND_NOTIFICATIONS_TO_ SUPERVISOR |
X |
1095 |
Boolean |
X |
|||
|
STATUS |
X |
512 |
Enumerated |
||||
|
SUPERVISORY_DEVICE_ PROCESS_ID |
X |
3052 |
Unsigned |
||||
|
USER_NAME |
X |
2390 |
Character String |
X |
400 characters max |
1 Not present in all instances.