Dynamically Creatable: No
Dynamically Deletable: No
|
Property Name |
Required |
Optional |
Proprietary |
Property ID |
Data Type |
Writable |
Range |
|---|---|---|---|---|---|---|---|
|
ACTION |
X |
2 |
X |
||||
|
CONTROLLED_VAR_UNITS |
20 |
X |
|||||
|
OBJECT_NAME |
X |
77 |
X |
||||
|
OUTPUT_UNITS |
82 |
X 1 |
|||||
|
OUT_OF_SERVICE |
X |
81 |
X 2 |
||||
|
PRESENT_VALUE |
X |
85 |
X 3 |
||||
|
PRIORITY_FOR_WRITING |
X |
88 |
X |
||||
|
SETPOINT |
X |
108 |
X1 |
||||
|
ACKED_TRANSITIONS 4 |
X |
0 |
|||||
|
BIAS |
X |
14 |
X2 |
||||
|
COV_INCREMENT 5 |
X |
22 |
X |
||||
|
DEADBAND |
X |
25 |
X |
0.0–10,000 |
|||
|
DERIVATIVE_CONSTANT |
X |
26 |
X2 |
||||
|
DERIVATIVE_CON_UNITS |
X |
27 |
X1 |
||||
|
DESCRIPTION |
X |
28 |
64 characters max |
||||
|
ERROR_LIMIT4 |
34 |
X 6 |
|||||
|
EVENT_DETECTION_ENABLE4 |
X |
353 |
|||||
|
EVENT_ENABLE4 |
35 |
X |
|||||
|
EVENT_MESSAGE_TEXTS4 |
X |
351 |
|||||
|
EVENT_MESSAGE_TEXTS_ CONFIG4 |
X |
352 |
X6 | 256 characters max | |||
|
EVENT_TIME_STAMPS4 |
X |
130 |
|||||
|
INTEGRAL_CONSTANT |
X |
49 |
X2 |
||||
|
INTEGRAL_CONST_UNITS |
X |
50 |
X |
||||
|
MAX_OUTPUT |
X |
61 |
X2 |
||||
|
MIN_OUTPUT |
X |
68 |
X2 |
||||
|
NOTIFICATION_CLASS4 |
X |
17 |
X6 |
1–4,194,303 |
|||
|
NOTIFY_TYPE4 |
X |
72 |
X6 |
||||
|
PROPORTIONAL_CONST |
X |
93 |
X2 |
||||
|
PROP_CONSTANT_UNITS |
X |
94 |
X1 |
||||
|
RELIABILITY |
X |
103 |
X3 |
||||
|
TIME_DELAY4 |
X |
113 |
X6 |
||||
|
UPDATE_INTERVAL |
X |
118 |
X1 |
||||
|
ALARM_STATE5 |
X |
1006 |
Enumerated |
X6 |
|||
|
ALARM_MESSAGE_TEXT |
X |
536 |
String |
X6 |
|||
|
BIAS_REF |
X |
4687 |
Complex |
||||
|
CNRL_DISPLAY_PRECISION5 |
X |
1488 |
Enumerated |
X |
|||
|
DERIVATIVE_CONST_REF |
X |
4686 |
Complex |
||||
|
DISPLAY_PRECISION |
X |
661 |
Enumerated |
X1 |
|||
|
ENABLED |
X |
673 |
Boolean |
X |
|||
|
EXECUTION_PRIORITY |
X |
2197 |
Enumerated |
X |
|||
|
GRAPHIC4 |
X |
32581 |
Object Reference |
X6 |
|||
|
GRAPHIC_ALIAS4 |
X |
32623 |
String |
X6 |
|||
|
INSTANCE_NUMBER5 |
X |
32589 |
Unsigned |
||||
|
INTEGRAL_CONST_REF |
X |
4685 |
Complex |
||||
|
ITEM_REFERENCE5 |
X |
32527 |
Character String |
||||
|
INTRINSIC_ALARM_DISABLED |
X |
4305 |
Boolean |
X6 |
|||
|
JCI_CONTROLLED_VAR_REF |
X |
4683 |
Complex |
||||
|
JCI_MANIPULATED_VAR_REF |
X |
4682 |
Complex |
||||
|
JCI_OUTOFSERVICE_REF |
X |
12201 |
Complex |
||||
|
JCI_OUTOFSERVICE_ VALUE_REF |
X |
12202 |
Complex |
||||
|
JCI_SETPOINT_REFERENCE |
X |
4690 |
Complex |
||||
|
LAST_KNOWN_TIME_STAMPS5 |
X |
1290 |
BACnet Array |
||||
|
MANUAL_TUNING5 |
X |
3408 |
Enumerated |
0-1 |
|||
|
MAPPED_NAME5 |
X |
2564 |
String |
||||
|
MAX_OUTPUT_REF |
X |
4688 |
Complex |
||||
|
MIN_OUTPUT_REF |
X |
4889 |
Complex |
||||
|
NOTIFICATION_OBJ_REF4 |
X |
4304 |
Complex |
X6 |
|||
|
OBJECT_CATEGORY |
X |
908 |
Enumerated |
X |
|||
|
OUTPUT_DISPLAY_PRECISION5 |
X |
1487 |
Enumerated |
X |
|||
|
PROPORTIONAL_CONST_REF |
X |
4684 |
Complex |
||||
|
REMOTE_DESCRIPTION5 |
X |
32519 |
Character String |
X |
|||
|
REMOTE_DEVICE_ADDRESS5 |
X |
538 |
Complex |
||||
|
STORED_EVENT_ENABLE |
X |
4306 |
Bit String |
||||
|
STATUS |
X |
512 |
Enumerated |
||||
|
USER_NAME |
X |
2390 |
String |
X |