Dynamically Creatable: No
Dynamically Deletable: No
|
Property Name |
Required |
Optional |
Proprietary |
Property ID |
Data Type |
Writable |
Range |
|---|---|---|---|---|---|---|---|
|
LIFE_SAFETY_MODE |
X |
160 |
X |
||||
|
OBJECT_NAME |
X |
77 |
X |
||||
|
OUT_OF_SERVICE |
X |
81 |
X |
||||
|
RELIABILITY |
X |
103 |
X |
||||
|
TRACKING_VALUE 1 |
X |
164 |
X |
0–65,535 |
|||
|
DESCRIPTION |
X |
28 |
X |
||||
|
DEVICE_TYPE |
X |
31 |
X |
||||
|
DIRECT_READING |
X |
156 |
X |
||||
|
MAINTENANCE_REQUIRED |
X |
158 |
X |
||||
|
MEMBER_OF |
X |
159 |
X |
||||
|
PROFILE_NAME |
X |
168 |
X |
||||
|
UNITS |
X |
117 |
X |
||||
|
ALARM_STATE |
X |
1006 |
Enumerated |
||||
|
ENABLED |
X |
673 |
Boolean |
X |
|||
|
EXECUTION_PRIORITY |
X |
2197 |
Enumerated |
X |
0–3 |
||
|
INSTANCE_NUMBER |
X |
32589 |
Unsigned |
||||
|
INTRINSIC_ALARM_DISABLED |
X |
4305 |
Boolean |
X |
|||
|
ITEM_REFERENCE |
X |
32527 |
Character String |
||||
|
LAST_KNOWN_TIME_STAMPS |
X |
1290 |
BACnet Array |
||||
|
MAPPED_NAME |
X |
2564 |
String |
||||
|
OBJECT_CATEGORY |
X |
908 |
Enumerated |
X |
|||
|
REMOTE_DESCRIPTION |
X |
32519 |
Character String |
X |
|||
|
REMOTE_DEVICE_ADDRESS |
X |
538 |
Complex |
||||
|
STATUS |
X |
512 |
Enumerated |
||||
|
STORED_EVENT_ENABLE |
X |
4306 |
BitString |
X |
|||
|
USER_NAME |
X |
2390 |
String |
X |
400 characters max |