Life Safety Zone - Metasys - LIT-12013310 - Server - Open Application Server - 13.0

Open Application Server (OAS) Protocol Implementation Conformance Statement

Brand
Metasys
Product name
Open Application Server
Document type
Protocol Implementation Conformance Statement
Document number
LIT-12013310
Version
13.0
Revision date
2023-11-08
Product status
Active
Language
English

Dynamically Creatable: No

Dynamically Deletable: No

Table 1. Life Safety Zone

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

LIFE_SAFETY_MODE

X

    160  

X

 

OBJECT_NAME

X

    77  

X

 

OUT_OF_SERVICE

X

    81  

X

 

RELIABILITY

X

   

103

 

X

 

TRACKING_VALUE 1

X

   

164

 

X

0–65,535

DESCRIPTION

 

X

 

28

 

X

 

DEVICE_TYPE

 

X

 

31

 

X

 

DIRECT_READING

 

X

 

156

 

X

 

MAINTENANCE_REQUIRED

 

X

 

158

 

X

 

MEMBER_OF

 

X

 

159

 

X

 

PROFILE_NAME

 

X

 

168

 

X

 

UNITS

 

X

 

117

 

X

 

ALARM_STATE

   

X

1006

Enumerated

   

ENABLED

   

X

673

Boolean

X

 

EXECUTION_PRIORITY

   

X

2197

Enumerated

X

0–3

INSTANCE_NUMBER

   

X

32589

Unsigned

   

INTRINSIC_ALARM_DISABLED

   

X

4305

Boolean

X

 

ITEM_REFERENCE

   

X

32527

Character String

   

LAST_KNOWN_TIME_STAMPS

   

X

1290

BACnet Array

   

MAPPED_NAME

   

X

2564

String

   

OBJECT_CATEGORY

   

X

908

Enumerated

X

 

REMOTE_DESCRIPTION

   

X

32519

Character String

X

 

REMOTE_DEVICE_ADDRESS

   

X

538

Complex

   

STATUS

   

X

512

Enumerated

   

STORED_EVENT_ENABLE

   

X

4306

BitString

X

 

USER_NAME

   

X

2390

String

X

400 characters max

1 Writable when Out of Service is True.