Dynamically Creatable: No
Dynamically Deletable: No
|
Property Name |
Required |
Optional |
Proprietary |
Property ID |
Data Type |
Writable |
Range |
|---|---|---|---|---|---|---|---|
|
APDU_TIMEOUT |
X |
11 |
X |
1,000–65,535 in milli-seconds |
|||
|
APPLICATION _SOFTWARE_ VERSION |
X |
12 |
X |
||||
|
MAX_APDU_ LENGTH_ACCEPTED |
X |
62 |
|||||
|
MSTP_APDU_LENGTH |
X |
1751 |
|||||
|
NUMBER_OF_ APDU_RETRIES |
X |
73 |
X |
||||
|
OBJECT_NAME |
X |
77 |
X |
||||
|
ACTIVE_COV _SUBSCRIPTIONS |
X |
152 |
|||||
|
APDU_SEGMENT _TIMEOUT |
X |
10 |
X |
1,000–65,535 in milliseconds |
|||
|
ALIGN_INTERVALS |
X |
193 |
X |
||||
|
BACKUP_FAILURE _TIMEOUT |
X |
153 |
X |
||||
|
CONFIGURATION _FILES |
X |
154 |
|||||
|
DAYLIGHT_ SAVINGS_STATUS |
X |
24 |
|||||
|
DESCRIPTION |
X |
28 |
X |
64 characters max |
|||
|
INTERVAL_OFFSET |
X |
195 |
X |
||||
|
LAST_RESTART _REASON |
X |
196 |
|||||
|
LAST_RESTORE _TIME |
X |
157 |
|||||
|
LOCAL_DATE |
X |
56 |
|||||
|
LOCAL_TIME |
X |
57 |
|||||
|
LOCATION |
X |
58 |
X |
||||
|
MAX_SEGMENTS _ACCEPTED |
X |
167 |
|||||
|
RESTART_ NOTIFICATION_ RECIPIENTS |
X |
202 |
X |
||||
|
TIME_OF_DEVICE _RESTART |
X |
203 |
|||||
|
TIME_ SYNCHRONIZATION_ INTERVAL |
X |
204 |
X |
0-1440 |
|||
|
TIME_ SYNCHRONIZATION_ RECIPIENTS |
X |
116 |
X |
||||
|
UTC_OFFSET |
X |
119 |
|||||
|
UTC_TIME_SYNC_ RECIPIENTS |
X |
206 |
X |
||||
|
ADS_REPOSITORY |
X |
32558 |
Complex |
X |
|||
|
ALARM_REPOSITORY _SIZE |
X |
32543 |
Unsigned |
X |
100–1,000 |
||
|
ALARM_SNOOZE _TIME |
X |
32544 |
Unsigned |
X |
0–75 |
||
|
ALARM_STATE |
X |
1006 |
Enumerated |
||||
|
ARCHIVE_DATE |
X |
849 |
Date |
||||
|
ARCHIVE_STATUS |
X |
1187 |
Unsigned |
||||
|
ARCHIVE_TIME |
X |
850 |
Time |
||||
|
AUTHORIZATION_ CATEGORY |
X |
908 |
Enumerated |
X |
0–249 |
||
|
BACNET_ BROADCAST_ RECEIVE_RATE |
X |
745 |
Unsigned |
||||
|
BACNET_IP_PORT |
X |
1223 |
Unsigned |
||||
|
COMPLETION_ DOMAINS |
X |
32532 |
List |
||||
|
COMPUTER_NAME |
X |
32531 |
String |
X |
40 characters max |
||
|
CONTACT_ PERSON |
X |
32554 |
String |
X |
|||
|
COV_RECEIVE_ RATE |
X |
650 |
Unsigned |
||||
|
COV_TRANSMIT_ RATE |
X |
651 |
Unsigned |
||||
|
CPU_USAGE |
X |
2583 |
Real |
||||
|
DEFAULT_ADS_ PRIORITY_THRESHOLD |
X |
2585 |
Unsigned |
0-225 |
|||
|
DEFAULT_BASE_ UNITS |
X |
2203 |
Enumerated |
||||
| DEVICE_UUID |
X |
1853 |
Octet String |
||||
|
DHCP_ENABLED |
X |
1138 |
Boolean |
X |
|||
|
DNS_SERVER_ IP_ADDRESS |
X |
32534 |
Complex |
X |
|||
|
DOMAIN_NAME |
X |
2334 |
String |
X |
|||
|
EMAIL_ AUTHENTIFICATION_ TYPE |
X |
3814 |
Enumerated |
X |
|||
|
EMAIL_DDA |
X |
32568 |
Complex |
X |
|||
|
EMAIL_ DIAGNOSTICS |
X |
3133 |
String |
||||
|
ENABLE_AUDIT_ LEVEL |
X |
32549 |
Unsigned |
X |
1–4 |
||
|
ENABLED |
X |
673 |
Boolean |
||||
|
ESTIMATED_FLASH _AVAILABLE |
X |
2395 |
Real |
||||
|
EXECUTION_PRIORITY |
X |
2197 |
Enumerated |
||||
|
EXTENDED_PROTO _VERSION |
X |
2291 |
Unsigned |
||||
|
EXTERNAL_MODEM _CONFIG |
X |
32530 |
Complex |
X |
|||
|
FAIL_EMAIL_ADDRESS |
X |
32542 |
Complex |
X |
|||
|
FLASH_USAGE |
X |
2584 |
Real |
||||
|
HOST_NAME |
X |
750 |
String |
||||
|
INCOMING_EVENT _RATE |
X |
1481 |
Unsigned |
||||
|
INTERNAL_MODEM _CONFIG |
X |
32529 |
Complex |
X |
|||
|
INTERNODE COMM_TIMER |
X |
845 |
Unsigned |
||||
| IP_COMM_MODE |
X |
1854 |
Enumerated |
X |
|||
|
IP_MASK |
X |
1136 |
Complex |
X |
|||
|
IP_ROUTER _ADDRESS |
X |
1137 |
Complex |
X |
|||
|
ITEM_REFERENCE |
X |
32527 |
Character String |
||||
|
JCI_IP_ADDRESS |
X |
1135 |
Complex |
X |
|||
|
JCI_STATUS |
X |
847 |
Enumerated |
||||
|
LAN_STATUS |
X |
32564 |
Enumerated |
||||
|
LAST_IDLE_SAMPLE |
X |
30082 |
Real |
||||
|
LOCAL_SITE_DIRECTOR |
X |
32557 |
Complex |
X |
|||
|
MAX_MESSAGE_BUFFER |
X |
848 |
Unsigned |
X |
|||
|
MEMORY_USAGE |
X |
2581 |
Real |
||||
|
NAME |
X |
2390 |
String |
X |
400 characters max |
||
|
NETWORK_TOLERANCE |
X |
864 |
Enumerated |
X |
|||
|
NUMBER_OF_ NXES_REPORTING |
X |
4821 |
Unsigned |
||||
|
OBJECT_MEMORY _USAGE |
X |
2582 |
Real |
||||
|
OBTAIN_DNS _ADDRESS |
X |
32533 |
Boolean |
X |
|||
| OPERATIONAL_CERTIFICATE_STATUS | X | 64821 | Structure | ||||
|
OUTGOING_EVENT _RATE |
X |
1480 |
Unsigned |
||||
|
PAGER_DDA |
X |
32569 |
Complex |
X |
|||
|
PAGER_DIAGNOSTICS |
X |
30100 |
String |
||||
|
ENABLE_BACNET/SC_DECRYPTION_FEATURE |
X |
1895 |
Boolean |
||||
|
PAGER_DIALUP_ CONFIG |
X |
32535 |
Complex |
X |
|||
|
PAGER_DIALUP_ STATUS |
X |
32565 |
Enumerated |
||||
|
POP_PASSWORD |
X |
32541 |
String |
X |
|||
|
POP_SERVER_ HOSTNAME |
X |
32539 |
String |
X |
|||
|
POP_USER_NAME |
X |
32540 |
String |
X |
|||
|
PORT_NUMBER |
X |
1180 |
Unsigned |
X |
0–65,535 |
||
|
PRINTER_DDA |
X |
32621 |
Complex |
X |
|||
|
PROCESS_ID_LIST |
X |
64010 |
Complex |
X |
|||
|
PROCESS_UNMAPPED_OBJECT_ALARMS |
X |
64584 |
Boolean |
X |
|||
|
READ_ONLY_ COMMUNITY |
X |
32555 |
String |
X |
|||
|
READ_WRITE_ COMMUNITY |
X |
32556 |
String |
X |
|||
|
SERVICE_TIME |
X |
63926 |
Unsigned |
||||
|
SMTP_PASSWORD |
X |
3861 |
String |
X |
|||
|
SMTP_PORT |
X |
32538 |
Unsigned |
X |
0–65,535 |
||
|
SMTP_SERVER_ HOST |
X |
32537 |
Complex |
X |
|||
|
SMTP_USER _NAME |
X |
3815 |
String |
X |
|||
|
SNMP_DDA |
X |
32570 |
Complex |
X |
|||
|
SNMP_ENABLED |
X |
32552 |
Boolean |
X |
|||
|
SNMP_MANAGEMENT _DEVICE |
X |
32553 |
Complex |
X |
|||
|
SNMP_VERSION |
X |
32622 |
Enumerated |
X |
|||
|
STATUS |
X |
512 |
Enumerated |
||||
|
TRANSFER_BUFFER_ FULL_WORST _TIME |
X |
857 |
Unsigned |