BACnet Interoperability Building Blocks (BIBBs) (Annex K) - Metasys - LIT-12013310 - Server - Open Application Server - 13.0

Open Application Server (OAS) Protocol Implementation Conformance Statement

Product
Building Automation Systems > Application Servers > Open Application Server
Document number
LIT-12013310
Version
13.0
Revision date
2023-11-08
Product status
Active

The following table lists all BIBBs that are supported. The table is divided into BIBBs required for the BACnet Building Controller (B-BC) profile, followed by additional BIBBs that are supported but not required for the B-BC profile.

Table 1. BACnet B-BC BIBBs Support

BIBB Name (A = Initiates and B = Executes)

Designation

Required for B-BC Profile

Alarm and Event - ACK - B

AE-ACK-B

Alarm and Event - Information - B

AE-INFO-B

Alarm and Event - Notification - Internal - B

AE-N-I-B

Device Management - Dynamic Device Binding - A

DM-DDB-A

Device Management - Dynamic Device Binding - B

DM-DDB-B

Device Management - Device Communication Control - B

DM-DCC-B

Device Management - Device Object Binding - B

DM-DOB-B

Device Management - Dynamic Time Synchronization - B

DM-TS-B

Device Management - Dynamic UTC Time Synchronization - B

DM-UTC-B

Device Management - Reinitialize Device - B

DM-RD-B

Device Management - Backup and Restore - B

DM-BR-B

Data Sharing - Read Property - A

DS-RP-A

Data Sharing - Read Property - B

DS-RP-B

Data Sharing - Read Property Multiple - A

DS-RPM-A

Data Sharing - Read Property Multiple - B

DS-RPM-B

Data Sharing - Write Property - A

DS-WP-A

Data Sharing - Write Property - B

DS-WP-B

Data Sharing - Write Property Multiple - B

DS-WPM-B

Scheduling - External - B

SCHED-E-B

Trending - Viewing and Modifying Trends Internal - B

T-VMT-I-B

Trending - Automated Trend Retrieval - B

T-ATR-B

Not Required for B-BC Profile

Alarm and Event - ACK - A

AE-ACK-A

Alarm and Event - Alarm Summary - B

AE-ASUM-B

Alarm and Event Management-Configurable Recipient Lists - B

AE-CRL-B

Alarm and Event - Notification - A

AE-N-A

Alarm and Event - Notification - External - B

AE-N-E-B

Alarm and Event - Enrollment Summary - B

AE-ESUM-B

Alarm and Event Management-Alarm Summary View-A

AE-AS-A

Device Management - Automatic Time Synchronization - A

DM-ATS-A

Device Management - Manual Time Synchronization - A

DM-MTS-A

Device Management - Device Object Binding - A

DM-DOB-A

Device Management - Restart - A

DM-R-A

Device Management - Restart - B

DM-R-B

Device Management - List Manipulation - A

DM-LM-A

Device Management - List Manipulation - B

DM-LM-B

Device Management - Object Creation and Deletion - B

DM-OCD-B

Device Management - Time Synchronization - A

DM-TS-A

Device Management - UTC Time Synchronization - A

DM-UTC-A

Data Sharing - COV - A

DS-COV-A

Data Sharing - COV - B

DS-COV-B

Data Sharing - COVP - A

DS-COVP-A

Data Sharing - COVP - B

DS-COVP-B

Data Sharing - COVU - A

DS-COVU-A

Data Sharing - COVU - B

DS-COVU-B

Data Sharing - Write Property Multiple - A

DS-WPM-A

Network Management- BBMD Configuration - B

NM-BBMDC-B

Network Management-Secure Connect Hub-B NM-SCH-B
Network Management-Secure Connect Direct Connect -A NM-SCDC-A
Network Management-Secure Connect Direct Connect -B NM-SCDC-B

Scheduling - Internal - B

SCHED-I-B

Scheduling - Weekly Schedule - A

SCHED-WS-A

Trending - View and Modify Trends - E - B

T-VMT-E-B