Schedule - Metasys - LIT-12013310 - Server - Open Application Server - 12.0

Open Application Server (OAS) Protocol Implementation Conformance Statement

Brand
Metasys
Product name
Open Application Server
Document type
Protocol Implementation Conformance Statement
Document number
LIT-12013310
Version
12.0
Revision date
2022-07-06
Product status
Active
Language
English

Dynamically Creatable: Yes

Dynamically Deletable: Yes

Table 1. Schedule

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

EFFECTIVE_PERIOD

X

   

32

 

X

 

LIST_OF_PROP_REFS

X

   

54

     

OBJECT_NAME

X

   

77

 

X

 

OUT_OF_SERVICE

X

   

81

 

X

 

PRESENT_VALUE

X

   

85

 

X 1

 

PRIORITY_FOR_WRITING

X

   

88

 

X

 

SCHEDULE_DEFAULT

X

   

174

 

X

 

DESCRIPTION

 

X

 

28

 

X

64 characters max

EXCEPTION_SCHEDULE

 

X

 

38

 

X 3

 

PROFILE_NAME 3

 

X

 

168

     

WEEKLY_SCHEDULE

 

X

 

123

 

X

 

ALARM_STATE

   

X

1006

Enumerated

   

BACNET_EXPOSED

   

X

3807

Boolean

X

 

COV_COUNT3

   

X

839

Byte

   

DEVICE_MAC_ADDRESS3

   

X

3629

Byte

   

DEVICE_TIME ZONE

   

X

1403

Enumerated

   

DISPLAY_UNITS3

   

X

2207

Enumerated

X

 

ENABLE_OBJECT_TYPE_ VALIDATION3

   

X

3983

Boolean

X

 

ENABLED

   

X

673

Boolean

X

 

EXCEPTION_SCHEDULE3

   

X

38

List

   

EXECUTION_PRIORITY

   

X

2197

Enumerated

X

0–3

IN_TEST3

   

X

3368

Boolean

   

INSTANCE_NUMBER

   

X

32589

Unsigned

   

ITEM_REFERENCE

   

X

32527

Character String

   

JCI_EXCEPTION_SCHEDULE

   

X

2573

List

X

 

JCI_LIST_OF_PROPERTY_REF

   

X

2574

List

X

 

MAPPED_NAME3

   

X

2564

String

   

OBJECT_CATEGORY

   

X

908

Enumerated

X

 

OFFLINE3

   

X

913

Boolean

   

PERFORM_INDEX3

   

X

965

Unsigned

   

REMOTE_DESCRIPTION3

   

X

32519

Character String

X

 

REMOTE_DEVICE_ADDRESS3

     

538

Complex

   

SCHEDULE_DATA_TYPE

   

X

951

Enumerated

X

 

SCHEDULE_TYPE

   

X

950

Enumerated

X

 

SICS_BEHAVIOR3

   

X

4349

Boolean

X

 

START_TIME_SCHEDULE_ VALUE3

   

X

1728

Enumerated

   

STATES TEXT3

   

X

931

Enumerated

X

 

STATUS

   

X

512

Enumerated

   

STOP_TIME_SCHEDULE_VALUE

   

X

1729

Enumerated

   

TODAYS_SCHEDULE3

   

X

4198

List

   

TRUNK_NUMBER3

   

X

549

Byte

   

USER_NAME

   

X

2390

Character String

X

400 characters max

1 Writable when OUT_OF_SERVICE is true.
2 Not writable in all instances.
3 Not present in all instances.