Dynamically Creatable: No
Dynamically Deletable: No
|
Property Name |
Required |
Optional |
Proprietary |
Property ID |
Data Type |
Writable |
Range |
|---|---|---|---|---|---|---|---|
|
OBJECT_NAME |
X |
77 |
X |
||||
|
APDU_LENGTH |
X |
399 |
X |
||||
|
BACNET_COMMAND |
X |
417 |
X |
||||
|
BACNET_IP_ADDRESS |
X |
400 |
|||||
|
BACNET_IP_MODE |
X |
408 |
|||||
|
BACNET_IP_UDP_PORT |
X |
412 |
|||||
|
BACNET_MAC_ADDRESS |
X |
423 |
|||||
|
BBMD_ACCEPT_FD_REGISTRATIONS |
X |
413 |
X |
||||
|
BBMD_BROADCAST_DISTRIBUTION_TABLE |
X |
414 |
X |
||||
|
BBMD_FOREIGN_DEVICE_TABLE |
X |
415 |
|||||
|
DESCRIPTION |
X |
28 |
X |
64 characters max |
|||
|
IP_DHCP_ENABLE |
X |
402 |
|||||
|
IP_DNS_SERVER |
X |
406 |
|||||
|
IP_SUBNET_MASK |
X |
411 |
|||||
|
NETWORK_NUMBER 1 |
X |
425 |
|||||
|
NETWORK_NUMBER QUALITY |
X |
426 |
|||||
|
ALARM_STATE |
X |
1006 |
Enumerated |
||||
|
BACNET_IP_PORT |
X |
1223 |
Unsigned |
X |
|||
|
BROADCAST_ADDRESS |
X |
2045 |
String |
||||
|
DEVICE_ADDRESS |
X |
876 |
String |
||||
|
DNS_REFRESH_PERIOD |
X |
2336 |
Unsigned |
X |
|||
|
ENABLED |
X |
673 |
Boolean |
X |
|||
|
EXECUTION_PRIORITY |
X |
2197 |
Enumerated |
X |
|||
|
ITEM_REFERENCE |
X |
32527 |
Enumerated |
||||
|
JCI_NPO_ADPU_RETRIES |
X |
1851 |
Unsigned |
X |
|||
|
JCI_NPO_ADPU_SEGMENT_TIMEOUT |
X |
1849 |
Unsigned |
X |
|||
|
JCI_NPO_ADPU_TIMEOUT |
X |
1850 |
Unsigned |
X |
|||
|
JCI_NPO_CHANGES_PENDING_BITSTRING |
X |
1852 |
Unsigned |
X |
|||
|
OBJECT_CATEGORY |
X |
908 |
Enumerated |
X |
|||
|
PROT_ENG_OUT_RESOURCE |
X |
2020 |
Unsigned |
||||
|
STATUS |
X |
512 |
Enumerated |
||||
|
USER_NAME |
X |
2390 |
String |
X |