Device - Metasys - LIT-12013310 - Server - Open Application Server - 12.0

Open Application Server (OAS) Protocol Implementation Conformance Statement

Brand
Metasys
Product name
Open Application Server
Document type
Protocol Implementation Conformance Statement
Document number
LIT-12013310
Version
12.0
Revision date
2022-07-06
Product status
Active
Language
English

Dynamically Creatable: No

Dynamically Deletable: No

Table 1. Device

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

APDU_TIMEOUT

X

   

11

 

X

1,000–65,535 in milli-seconds

APPLICATION _SOFTWARE_ VERSION

X

   

12

 

X

 

MAX_APDU_ LENGTH_ACCEPTED

X

   

62

 

 

NUMBER_OF_ APDU_RETRIES

X

   

73

 

X

 

OBJECT_NAME

X

   

77

 

X

 

ACTIVE_COV _SUBSCRIPTIONS

 

X

 

152

     

ADPU_SEGMENT _TIMEOUT

 

X

 

10

 

X

1,000–65,535 in milliseconds

ALIGN_INTERVALS

 

X

 

193

 

X

 

BACKUP_FAILURE _TIMEOUT

 

X

 

153

 

X

 

CONFIGURATION _FILES

 

X

 

154

     

DAYLIGHT_ SAVINGS_STATUS

 

X

 

24

     

DESCRIPTION

 

X

 

28

 

X

64 characters max

INTERVAL_OFFSET

 

X

 

195

 

X

 

LAST_RESTART _REASON

 

X

 

196

     

LAST_RESTORE _TIME

 

X

 

157

     

LOCAL_DATE

 

X

 

56

     

LOCAL_TIME

 

X

 

57

     

LOCATION

 

X

 

58

 

X

 

MAX_SEGMENTS _ACCEPTED

 

X

 

167

     

RESTART_ NOTIFICATION_ RECIPIENTS

 

X

 

202

 

X

 

TIME_OF_DEVICE _RESTART

 

X

 

203

     

TIME_ SYNCHRONIZATION_ INTERVAL

 

X

 

204

 

X

0-1440

TIME_ SYNCHRONIZATION_ RECIPIENTS

 

X

 

116

 

X

 

UTC_OFFSET

 

X

 

119

     

UTC_TIME_SYNC_ RECIPIENTS

 

X

 

206

 

X

 

ADS_REPOSITORY

   

X

32558

Complex

X

 

ALARM_REPOSITORY _SIZE

   

X

32543

Unsigned

X

100–1,000

ALARM_SNOOZE _TIME

   

X

32544

Unsigned

X

0–75

ALARM_STATE

   

X

1006

Enumerated

   

ARCHIVE_DATE

   

X

849

Date

   

ARCHIVE_STATUS

   

X

1187

Unsigned

   

ARCHIVE_TIME

   

X

850

Time

   

AUTHORIZATION_ CATEGORY

   

X

908

Enumerated

X

0–249

BACNET_ BROADCAST_ RECEIVE_RATE

   

X

745

Unsigned

   

BACNET_IP_PORT

   

X

1223

Unsigned

X

 

COMPLETION_ DOMAINS

   

X

32532

List

   

COMPUTER_NAME

   

X

32531

String

X

40 characters max

CONTACT_ PERSON

   

X

32554

String

X

 

COV_RECEIVE_ RATE

   

X

650

Unsigned

   

COV_TRANSMIT_ RATE

   

X

651

Unsigned

   

CPU_USAGE

   

X

2583

Real

   

DEFAULT_ADS_ PRIORITY_THRESHOLD

   

X

2585

Unsigned

 

0-225

DEFAULT_BASE_ UNITS

   

X

2203

Enumerated

   
DEVICE_UUID

X

 

X

1853

Octet String

   

DHCP_ENABLED

   

X

1138

Boolean

X

 

DNS_SERVER_ IP_ADDRESS

   

X

32534

Complex

X

 

DOMAIN_NAME

   

X

2334

String

X

 

EMAIL_ AUTHENTIFICATION_ TYPE

   

X

3814

Enumerated

X

 

EMAIL_DDA

   

X

32568

Complex

X

 

EMAIL_ DIAGNOSTICS

   

X

3133

String

   

ENABLE_AUDIT_ LEVEL

   

X

32549

Unsigned

X

1–4

ENABLED

   

X

673

Boolean

   

ESTIMATED_FLASH _AVAILABLE

   

X

2395

Real

   

EXECUTION_PRIORITY

   

X

2197

Enumerated

   

EXTENDED_PROTO _VERSION

   

X

2291

Unsigned

   

EXTERNAL_MODEM _CONFIG

   

X

32530

Complex

X

 

FAIL_EMAIL_ADDRESS

   

X

32542

Complex

X

 

FLASH_USAGE

   

X

2584

Real

   

HOST_NAME

   

X

750

String

   

INCOMING_EVENT _RATE

   

X

1481

Unsigned

   

INTERNAL_MODEM _CONFIG

   

X

32529

Complex

X

 

INTERNODE COMM_TIMER

   

X

845

Unsigned

   
IP_COMM_MODE    

X

1854

Enumerated

X

 

IP_MASK

   

X

1136

Complex

X

 

IP_ROUTER _ADDRESS

   

X

1137

Complex

X

 

ITEM_REFERENCE

   

X

32527

String

   

JCI_IP_ADDRESS

   

X

1135

Complex

X

 

JCI_STATUS

   

X

847

Enumerated

   

LAN_STATUS

   

X

32564

Enumerated

   

LAST_IDLE_SAMPLE

   

X

30082

Real

   

LOCAL_SITE_DIRECTOR

   

X

32557

Complex

X

 

MAX_MESSAGE_BUFFER

   

X

848

Unsigned

X

 

MEMORY_USAGE

   

X

2581

Real

   

NAME

   

X

2390

String

X

400 characters max

NETWORK_TOLERANCE

   

X

864

Enumerated

X

 

NUMBER_OF_ NXES_REPORTING

   

X

4821

Unsigned

   

OBJECT_MEMORY _USAGE

   

X

2582

Real

   

OBTAIN_DNS _ADDRESS

   

X

32533

Boolean

X

 
OPERATIONAL_CERTIFICATE_STATUS     X 64821 Structure    

OUTGOING_EVENT _RATE

   

X

1480

Unsigned

   

PAGER_DDA

   

X

32569

Complex

X

 

PAGER_DIAGNOSTICS

   

X

30100

String

   

ENABLE_BACNET/SC_DECRYPTION_FEATURE

   

X

1895

Boolean

   

PAGER_DIALUP_ CONFIG

   

X

32535

Complex

X

 

PAGER_DIALUP_ STATUS

   

X

32565

Enumerated

   

POP_PASSWORD

   

X

32541

String

X

 

POP_SERVER_ HOSTNAME

   

X

32539

String

X

 

POP_USER_NAME

   

X

32540

String

X

 

PORT_NUMBER

   

X

1180

Unsigned

X

0–65,535

PRINTER_DDA

   

X

32621

Complex

X

 

PROCESS_ID_LIST

   

X

64010

Complex

X

 

READ_ONLY_ COMMUNITY

   

X

32555

String

X

 

READ_WRITE_ COMMUNITY

   

X

32556

String

X

 

SERVICE_TIME

   

X

63926

Unsigned

   

SMTP_PASSWORD

   

X

3861

String

X

 

SMTP_PORT

   

X

32538

Unsigned

X

0–65,535

SMTP_SERVER_ HOST

   

X

32537

Complex

X

 

SMTP_USER _NAME

   

X

3815

String

X

 

SNMP_DDA

   

X

32570

Complex

X

 

SNMP_ENABLED

   

X

32552

Boolean

X

 

SNMP_MANAGEMENT _DEVICE

   

X

32553

Complex

X

 

SNMP_VERSION

   

X

32622

Enumerated

X

 

STATUS

   

X

512

Enumerated

   

TRANSFER_BUFFER_

FULL_WORST _TIME

   

X

857

Unsigned

   
Note: For the ADPU properties, write does not take effect until after reboot.