Command Object - Metasys - LIT-12013310 - Server - Open Application Server - 12.0

Open Application Server (OAS) Protocol Implementation Conformance Statement

Brand
Metasys
Product name
Open Application Server
Document type
Protocol Implementation Conformance Statement
Document number
LIT-12013310
Version
12.0
Revision date
2022-07-06
Product status
Active
Language
English

Dynamically Creatable: No

Dynamically Deletable: No

Table 1. Command Object

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

OBJECT_NAME

X

   

77

 

X

 

PRESENT_VALUE

X

   

85

 

X

 

ACTION_TEXT

 

X

 

3

 

X

60 characters max

DESCRIPTION

 

X

 

28

 

X

64 characters max

ALARM_STATE

   

X

1006

Enumerated

   

COMMAND_COUNT

   

X

1545

Unsigned

   

ENABLED

   

X

673

Boolean

X

 

EXECUTION_PRIORITY

   

X

2197

Enumerated

X

0–3

INSTANCE_NUMBER 1

   

X

32589

Unsigned

   

ITEM_REFERENCE

   

X

32527

Character String

   

MAPPED_NAME1

   

X

2564

String

   

OBJECT_CATEGORY

   

X

908

Enumerated

   

REMOTE_DESCRIPTION1

   

X

32519

Character String

X

 

REMOTE_DEVICE_ADDR1

   

X

538

Complex

   

STATES_TEXT

   

X

931

Enumerated

X 2

 

STATES_TEXT_ERROR_STATUS

   

X

64022

Enumerated

   

STATUS

   

X

512

Enumerated

   

USER_NAME

   

X

2390

Character String

X

 

USER_SELECTED_STATES_TEXT

   

X

1103

Boolean

X

 
1 Not present in all instances.
2 Not writable in all instances.