Calendar - Metasys - LIT-12013310 - Server - Open Application Server - 12.0

Open Application Server (OAS) Protocol Implementation Conformance Statement

Brand
Metasys
Product name
Open Application Server
Document type
Protocol Implementation Conformance Statement
Document number
LIT-12013310
Version
12.0
Revision date
2022-07-06
Product status
Active
Language
English

Dynamically Creatable: Yes

Dynamically Deletable: Yes

Table 1. Calendar

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

DATE_LIST

X

   

23

 

X

 

OBJECT_NAME

X

   

77

 

X

 

DESCRIPTION

 

X

 

28

 

X

64 characters max

ALARM_STATE

   

X

1006

Enumerated

   

ALLOW_CALENDAR_EDIT

   

X

64005

Enumerated

 

DATE_LIST_CHAGNED

   

X

1098

Byte

   

GLOBAL_CALENDAR_OBJECT_ REFERENCE

   

X

63914

Object Reference

X

 

GLOBAL_CALENDAR_UPDATE

   

X

1097

Structure

   

ENABLED

   

X

673

Boolean

X

 

EXECUTION_PRIORITY

   

X

2197

Enumerated

X

0–3

ITEM_REFERENCE

   

X

32527

Character String

   

OBJECT_CATEGORY

   

X

908

Enumerated

X

 

STATUS

   

X

512

Enumerated

   

USER_NAME

   

X

2390

Character String

X

400 characters max