Dynamically Creatable: No
Dynamically Deletable: No
|
Property Name |
Required |
Optional |
Proprietary |
Property ID |
Data Type |
Writable |
Range |
|---|---|---|---|---|---|---|---|
|
OBJECT_NAME |
X |
77 |
X |
||||
|
OUT_OF_SERVICE |
X |
81 |
X |
||||
|
POLARITY |
X |
84 |
X |
||||
|
PRESENT_VALUE |
X |
85 |
X 1 |
||||
|
ACTIVE_TEXT |
X |
4 |
|||||
|
ACTIVE_TIME_RESET |
X |
114 |
X |
||||
|
ACKED_TRANSITIONS 2 |
X |
0 |
|||||
|
ALARM_VALUE2 |
X |
6 |
X 3 |
||||
|
COS_COUNT |
X |
15 |
X |
||||
|
COS_TIME |
X |
16 |
|||||
|
DESCRIPTION |
X |
28 |
X |
64 characters max |
|||
|
DEVICE_TYPE |
X |
31 |
X |
||||
|
ELAPSED_ACTIVE_TIME2 |
X |
33 |
X |
||||
|
EVENT_DETECTION_ENABLE2 |
X | 353 | |||||
|
EVENT_ENABLE2 |
X |
35 |
X3 |
||||
|
EVENT_MESSAGE_TEXTS2 |
X |
351 | |||||
| EVENT_MESSAGE_TEXTS_ CONFIG2 | X | 352 | X3 | 256 characters max | |||
|
EVENT_TIME_STAMPS2 |
X |
130 |
|||||
|
INACTIVE_TEXT |
X |
46 |
|||||
|
NOTIFICATION_CLASS2 |
X |
17 |
X3 |
1–4,194,303 |
|||
|
NOTIFY_TYPE2 |
X |
72 |
X3 |
||||
|
RELIABILITY |
X |
103 |
X1 |
||||
|
STATE_COUNT_RESET |
X |
115 |
X |
||||
|
TIME_DELAY2 |
X |
113 |
X3 |
0–65,535 |
|||
|
ALARM_MESSAGE_TEXT |
X |
536 |
Character String |
X3 |
|||
|
ALARM_STATE |
X |
1006 |
Enumerated |
||||
|
BACNET_EXPOSED |
X |
536 |
String |
X |
|||
|
DEBOUNCE |
X |
610 |
Unsigned |
||||
|
ENABLED |
X |
673 |
Boolean |
X |
|||
|
EXECUTION_PRIORITY |
X |
2197 |
Enumerated |
X |
0–3 |
||
|
INTRINSIC_ALARM_DISABLED |
X |
4305 |
Boolean |
X |
|||
|
ITEM_REFERENCE |
X |
32527 |
Character String |
||||
|
GRAPHIC |
X |
32581 |
Character String |
X3 |
|||
|
GRAPHIC_ALIAS |
X |
32623 |
Character String |
X3 |
|||
|
OBJECT_CATEGORY |
X |
908 |
Enumerated |
X |
|||
|
OFFLINE |
X |
913 |
Boolean |
||||
|
OUT_OF_SERVICE_EXPIRATION_TIME |
X |
64787 |
Structure |
||||
|
NOTIFICATION_OBJ_REF |
X |
4304 |
Object Reference |
||||
|
SAB_MAC_ADDR |
X |
3645 |
Byte |
||||
|
SLOT |
X |
519 |
Unsigned |
||||
|
STATES_TEXT |
X |
931 |
Enumerated |
X 4 |
|||
|
STATUS |
X |
512 |
Enumerated |
||||
|
STORED_EVENT_ENABLE |
X |
4306 |
BitString |
||||
|
TROUBLE |
X |
810 |
Boolean |
||||
|
USER_NAME |
X |
2390 |
Character String |
X |
400 characters max |