Averaging - Metasys - LIT-12013310 - Server - Open Application Server - 12.0

Open Application Server (OAS) Protocol Implementation Conformance Statement

Brand
Metasys
Product name
Open Application Server
Document type
Protocol Implementation Conformance Statement
Document number
LIT-12013310
Version
12.0
Revision date
2022-07-06
Product status
Active
Language
English

Dynamically Creatable: No

Dynamically Deletable: No

Table 1. Averaging

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

ATTEMPTED_SAMPLES

X

   

124

 

X

 

OBJECT_NAME

X

   

77

 

X

 

WINDOW_INTERVAL

X

   

147

 

X

 

WINDOW_SAMPLES

X

   

148

 

X

 

DESCRIPTION

 

X

 

28

 

X

64 characters max

MIN_VALUE_TIMESTAMP

 

X

 

150

     

MAX_VALUE_TIMESTAMP

 

X

 

149

     

ALARM_STATE

   

X

1006

Enumerated

   

CURRENT_RELIABILITY

   

X

3377

Enumerated

   

ENABLED

   

X

673

Boolean

X

 

EXECUTION_PRIORITY

   

X

2197

Enumerated

X

0–3

INPUT_REF 1

   

X

545

Attribute Reference

   

INSTANCE_NUMBER1

   

X

32589

Unsigned

   

ITEM_REFERENCE

   

X

32527

Character String

   

MAPPED_NAME

   

X

2564

String

   

OBJECT_CATEGORY

   

X

908

Enumerated

X

 

REMOTE_DESCRIPTION1

   

X

32519

Character String

X

 

REMOTE_DEVICE_ADDRESS1

   

X

538

Complex

   

STATUS

   

X

512

Enumerated

   

USER_NAME

   

X

2390

Character String

X

400 characters max

1 Not present in all instances.