Set the time zone first, then either set the date and time or select a time server for the Site Director.

See the Verifying the Site Director defined for an engine/server and Setting the time synchronization method sections before following the steps in this section.

Notes:
  • If you select a site time server for your Site Director, and you also set the time manually in the OAS, the manual time is overridden at the end of the time specified in the Time Sync Period attribute (default is 1 hour).