Enabling Single Sign On with the Keep Me Signed In feature for ADFS Accounts - Metasys - LIT-12011279 - General System Information - Metasys System - 13.0

Network and IT Guidance Technical Bulletin

Product
Building Automation Systems > Building Automation Systems > Metasys System
Document number
LIT-12011279
Version
13.0
Revision date
2023-09-29
Product status
Active

Microsoft’s Keep Me Signed In feature is disabled by default with ADFS. To enable Keep Me Signed In, complete the following steps:

Procedure

  1. On the ADFS server, run the PowerShell command Set- AdfsProperties -EnableKmsi $true.
    Figure 1. PowerShell

  2. Go to the Metasys UI browser and click LOG IN WITH MY ORGANIZATIONAL ACCOUNT (ADFS). Enter your user name and password and click the Keep me signed in checkbox. This creates a cookie with a lifetime of 24 hours so that each time you come back to the Metasys UI application, it automatically logs you in. Click Sign In.
  3. Close your browser and open it back up.
  4. Open the Metasys UI to automatically log you in.