Example #2 - Metasys - LIT-12011279 - General System Information - Metasys System - 13.0

Network and IT Guidance Technical Bulletin

Brand
Metasys
Product name
Metasys System
Document type
Technical Bulletin
Document number
LIT-12011279
Version
13.0
Revision date
2023-09-29
Product status
Active
Language
English

1.3.6.1.4.1.4399.2.1.1.1.1.4.1.1.1006.10.69.110.101.114.103.121.46.66.86.49

Returned Value: point alarm state of a Metasys object called Energy.BV1.

In this example, the Alarm State attribute breaks out as:

1.3.6.1.4.1.4399.2.1.1.1.1.4.1.1.1006

The name of the Metasys point breaks out as:

10.69.110.101.114.103.121.46.66.86.49

where the first digit (10) is the length, and the remaining digits are the ASCII representations of the letters (Energy.BV1).