Example #1 - Metasys - LIT-12011279 - General System Information - Metasys System - 13.0

Network and IT Guidance Technical Bulletin

Brand
Metasys
Product name
Metasys System
Document type
Technical Bulletin
Document number
LIT-12011279
Version
13.0
Revision date
2023-09-29
Product status
Active
Language
English

1.3.6.1.4.1.4399.2.1.1.1.1.4.1.1.85.3.65.86.49

Returned value: present value of Metasys object called AV1.

In this example, the Present Value attribute breaks out as:

1.3.6.1.4.1.4399.2.1.1.1.1.4.1.1.85

The name of the Metasys point breaks out as:

3.65.86.49

where the first digit (3) is the length, and the remaining digits are the ASCII representations of the letters (AV1).