We recommend that you set RabbitMQ to restart after first, second, and
subsequent failures.
To set recovery action:
Procedure
In Control Panel, select Administrative Tools.
Double-click Services.
Right-click RabbitMQ and
select Properties. The RabbitMQ
Properties dialog box appears.
Click the Recovery Tab and under the First failure, Second
failure, and Subsequent failures drop-down list boxes, select Restart the Service.
Click OK.
Note:At Release 10.0 and later, RabbitMQ replaces MSMQ. See the following
table for each release and its queuing technology.
Table 1. Metasys Release and queuing technology
Metasys Release
MSMQ
RabbitMQ
Release 9.0 and earlier
X
-
Release 10.0 and Release 10.1
X
X
Release 11.0 and later
-
X
1 Both MSMQ and RabbitMQ are in use
at Release 10.0 and Release 10.1. 1
2 MSMQ is not used for queuing data at
Release 11.0 and later. MSMQ is still enabled at
Release 11.0 for legacy support and backward
compatibility purposes only.2