About this task

We recommend that you set MSMQ to restart after first, second, and subsequent failures.

To set recovery action:

Procedure

  1. In Control Panel, select Administrative Tools.
  2. Double-click Services.
  3. Right-click Message Queuing and select Properties. The Message Queuing Properties dialog box appears.
  4. On the Recovery Tab (in the First failure, Second failure, and Subsequent failures drop-down list boxes), select Restart the Service.
  5. Click OK.
    Note: At Release 10.0 and later, RabbitMQ replaces MSMQ. RabbitMQ is a service bus that sends notification messages to other services and for inter-process communication messages on the server.