Verifying the server certificate chain - Metasys - LIT-12011279 - General System Information - Metasys System - 13.0.50

Network and IT Guidance Technical Bulletin

Product
Building Automation Systems > Building Automation Systems > Metasys System
Document number
LIT-12011279
Version
13.0.50
Revision date
2024-01-26
Product status
Active

About this task

To verify a certificate chain for a Metasys server or SCT computer:

Procedure

  1. In Control Panel, select System and Security > Administrative Tools and double-click Internet Information Services (IIS) Manager. The IIS main screen appears.
  2. Highlight the name of the web server.
  3. Under the IIS section in the middle pane, double-click Server Certificates. The Server Certificates panel appears.
  4. On the Actions pane, click View. The Certificate screen appears.
  5. Click the Certification Path tab. The certificate chain appears.
  6. Click OK to close the certificate view.