The KNX integration uses a specific enumeration to extract field values in a compact (raw bitmap) format. It is represented by field point parameter 3. The KNX programmer provides the EIS or DPT type for all groups handled by the Metasys system. Table 1 shows the relationship between the enumeration and the EIS and DPT types.
|
Value type |
Metasys data type |
Type description |
EIS type |
DPT type |
|---|---|---|---|---|
|
0 |
- |
- |
- |
- |
|
1 |
AI, AO |
Unsigned Long (32 Bits) |
EIS11 Counter (32 bits) |
DPT 12 |
|
2 |
AI, AO |
Signed Long (32 Bits) |
EIS11 Counter (32 bits) |
DPT 13 |
|
3 |
AI, AO |
Signed Short (16 Bits) |
EIS10 Counter (16 bits) |
DPT 8 |
|
4 |
AI, AO |
Unsigned Short (16 Bits) |
EIS10 Counter (16 bits) |
DPT 7 |
|
5 |
AI, AO |
Float (4 byte) |
EIS9 Float (32 bits) |
DPT 14 |
|
6 |
AI, AO |
Unsigned Byte (8 Bits) |
EIS14 Counter (8 bits) EIS6 Scaling |
DPT 5 DPT 5 |
|
7 |
AI, AO |
Signed Byte (8 Bits) |
EIS14 Counter (8 bits) |
DPT 6 |
|
8 |
BI, BO |
Boolean (1 Bit) |
EIS1 Switching |
DPT 1 |
|
9 |
AI, AO |
Float (2 byte) |
EIS5 Float (16 bits) |
DPT 9 |