Schedule - Metasys - LIT-12011924 - Supervisory Device - Network Engine - 9.0

NIEx9 Protocol Implementation Conformance Statement

Brand
Metasys
Product name
Network Engine
Document type
Protocol Implementation Conformance Statement
Document number
LIT-12011924
Version
9.0
Language
English

Dynamically Creatable: Yes

Dynamically Deletable: Yes

Table 1. Schedule

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

EFFECTIVE_PERIOD

X

   

32

 

X

 

OBJECT_PROPERTY_REF

X

    78  

X

 

OBJECT_NAME

X

   

77

 

X

 

OUT_OF_SERVICE

X

   

81

 

X

 

PRESENT_VALUE

X

   

85

 

X1

 

PRIORITY_FOR_WRITING

X

   

88

 

X

 

SCHEDULE_DEFAULT

X

   

174

 

X

 

DESCRIPTION

 

X

 

28

 

X

64 characters max

EXCEPTION_SCHEDULE

 

X

 

38

 

X

 

WEEKLY_SCHEDULE

 

X

 

123

 

X

 

ALARM_STATE

   

X

1006

Enumerated

   

AUTHORIZATION_CATEGORY

   

X

908

Enumerated

X

0–249

DEVICE TIME ZONE

   

X

1403

Enumerated

   

ENABLED

   

X

673

Boolean

X

 

EXECUTION_PRIORITY

   

X

2197

Enumerated

X

0–3

ITEM_REFERENCE

   

X

32527

CharacterString

   

JCI_EXCEPTION_SCHEDULE

   

X

2573

List

X

 

JCI_LIST_OF_PROPERTY_ REF

   

X

2574

List

X

 

REMOTE_DESCRIPTION

   

X2

32519

CharacterString

X

 

REMOTE_DEVICE_ADDR

   

X2

538

Complex

   

REMOTE_OBJECT_NAME

   

X2

2564

CharacterString

   

STATES TEXT

   

X

931

Enumerated

X

 

STATUS

   

X

512

Enumerated

   

USER_NAME

   

X

2390

CharacterString

X

400 characters max

1 Writable when OUT_OF_SERVICE is true.
2 Not present in all instances.