Notification Class - Metasys - LIT-12011924 - Supervisory Device - Network Engine - 9.0

NIEx9 Protocol Implementation Conformance Statement

Brand
Metasys
Product name
Network Engine
Document type
Protocol Implementation Conformance Statement
Document number
LIT-12011924
Version
9.0
Language
English

Dynamically Creatable: Yes

Dynamically Deletable: Yes

Table 1. Notification Class

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

ACK_REQUIRED

X

    1  

X

 

OBJECT_NAME

X

   

77

 

X

 

PRIORITY

X

    86  

X

 

RECIPIENT_LIST

X

    102  

X

 

DESCRIPTION

 

X

  28  

X

64 characters max

ALARM_STATE

   

X

1006

Enumerated

   

AUTHORIZATION_CATEGORY

   

X

908

Enumerated

X

0–249

ENABLED

   

X

673

Boolean

X

 

EXECUTION_PRIORITY

   

X

2197

Enumerated

X

0–3

ITEM_REFERENCE

   

X

32527

CharacterString

   

REMOTE_DESCRIPTION

   

X1

32519

CharacterString

X

 

REMOTE_DEVICE_ADDR

   

X1

538

Complex

   

REMOTE_OBJECT_NAME

   

X1

2564

CharacterString

   

STATUS

   

X

512

Enumerated

   

USER_NAME

   

X

2390

CharacterString

X

400 characters max

1 Not present in all instances.