Event Enrollment - Metasys - LIT-12011924 - Supervisory Device - Network Engine - 9.0

NIEx9 Protocol Implementation Conformance Statement

Brand
Metasys
Product name
Network Engine
Document type
Protocol Implementation Conformance Statement
Document number
LIT-12011924
Version
9.0
Language
English

Dynamically Creatable: Yes

Dynamically Deletable: Yes

Table 1. Event Enrollment

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

EVENT_ENABLE

X

   

35

 

X

 

EVENT_PARAMETERS

X

   

83

 

X

 

NOTIFICATION_CLASS

X

   

17

 

X

1–4, 194,303

NOTIFY_TYPE

X

   

72

 

X

 

OBJECT_NAME

X

    77  

X

 

OBJECT_PROPERTY_REFERENCE

X

   

78

 

X1

 

RELIABILITY

X

   

103

     

DESCRIPTION

 

X

 

28

 

X

64 characters max

EVENT_MESSAGE_TEXTS

 

X

  351      

ALARM_MESSAGE_TEXT

   

X

536

CharacterString

X

 

ALARM_STATE

   

X

1006

Enumerated

   

AUTHORIZATION_CATEGORY

   

X

908

Enumerated

X

0–249

ENABLED

   

X

673

Boolean

X

 

EXECUTION_PRIORITY

   

X

2197

Enumerated

X

0–3

GRAPHIC

   

X

32581

CharacterString

X

 

GRAPHIC_ALIAS

   

X

32623

CharacterString

X

 

INPUT_REF

   

X

545

Complex

   

ITEM_REFERENCE

   

X

32527

Character tring

   

JCI_EVENT_PARAMETERS

   

X

2571

CharacterString

X

 

REMOTE_DESCRIPTION

   

X2

32519

CharacterString

X

 

REMOTE_DEVICE_ADDR

   

X2

538

Complex

   

REMOTE_OBJECT_NAME

   

X2

2564

CharacterString

   

STATUS

   

X

512

Enumerated

   

USER_NAME

   

X

2390

CharacterString

X

400 characters max

1 Only writable when not defined after create object.
2 Not present in all instances.