Device - Metasys - LIT-12011924 - Supervisory Device - Network Engine - 9.0

NIEx9 Protocol Implementation Conformance Statement

Brand
Metasys
Product name
Network Engine
Document type
Protocol Implementation Conformance Statement
Document number
LIT-12011924
Version
9.0
Language
English

Dynamically Creatable: No

Dynamically Deletable: No

Table 1. Device

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

APDU_RETRIES

X

   

73

 

X1

 

APDU_TIMEOUT

X

   

11

 

X1

1,000–65,535 in milli-seconds

APP_SW_VERSION

X

   

12

 

X

 

MAX_APDU_LENGTH_ACCEPTED

X

   

62

 

X1

 

OBJECT_NAME

X

   

77

 

X

 

ACTIVE_COV_SUBSCRIPTIONS

 

X

 

152

     

ADPU_SEGMENT_TIMEOUT

 

X

 

10

 

X1

1,000–65,535 in milli-seconds

ALIGN_INTERVALS

 

X

 

193

 

X

 

BACKUP_AND_RESTORE_ STATE

 

X

 

338

     

BACKUP_FAIL_TIMEOUT

 

X

 

153

 

X

 

BACKUP_PREPARATION_ TIME

 

X

 

339

     

CONFIG_FILES

 

X

 

154

     

DST_STATUS

 

X

 

24

     

DESCRIPTION

 

X

 

28

 

X

64 characters max

INTERVAL_OFFSET

 

X

 

195

 

X

 

LAST_RESTART_REASON

 

X

 

196

     

LOCAL_DATE

 

X

 

56

     

LOCAL_TIME

 

X

 

57

     

LOCATION

 

X

 

58

 

X

 

MAX_INFO_FRAMES

 

X

 

63

 

X

 

MAX_MASTER

 

X

  64  

X

1–127

MAX_SEGMENTS_ACCEPTED

 

X

  167      

RESTART_NOTIFICATION_ RECIPIENTS

 

X

 

202

 

X

 

RESTORE_PREPARATION_TIME

 

X

 

341

     

RESTORE_COMPLETION_TIME

 

X

 

340

     

TIME_OF_DEVICE_ RESTART

 

X

 

203

     

TIME_SYNCHRONIZATION_INTERVAL

 

X

 

204

 

X

1-1440

UTC_TIME_SYNCHRONIZATION_RECIPIENTS

 

X

 

206

 

X

 

UTC_OFFSET

 

X

  119      

TIME_SYNC_RECIPIENTS

 

X

  116  

X

 

ADS_CONNECTION_TYPE

   

X

32559

Enumerated

X

 

ADS_DELIVERY_TIME

   

X

32560

Time

X

 

ADS_DIAL_PRIORITY_THRESHOLD

   

X

2586

Unsigned

 

0–255

ADS_DIALUP_STATUS

   

X

32566

Enumerated

   

ADS_RESPOSITORY

   

X

32558

Complex

X

 

ALARM_RESPOSITORY_ SIZE

   

X

32543

Unsigned

X

100–1,000

ALARM_SNOOZE_TIME

   

X

32544

Unsigned

X

0–75

ALARM_STATE

   

X

1006

Enumerated

   

ARCHIVE_DATE

   

X

849

Date

   

ARCHIVE_STATUS

   

X

1187

Unsigned

   

ARCHIVE_TIME

   

X

850

Time

   

AUDIT_ACTION_WHEN_ FULL

   

X

32547

Enumerated

X

 

AUDIT_FORWARDING_THRESHOLD

   

X

32546

Unsigned

X

1–100

AUDIT_GENERATE_ALARM_WHEN_FULL

   

X

32548

Boolean

X

 

AUDIT_RESPOSITORY_SIZE

   

X

32545

Unsigned

X

10–500

AUTHORIZATION_ CATEGORY

   

X

908

Enumerated

X

0–249

BACNET_BROADCAST_RECEIVE_RATE

   

X

745

Unsigned

   

BACNET_IP_PORT

   

X

1223

Unsigned

X

 

BATTERY_CHARGING

   

X2

3563

Boolean

   

BATTERY_CONDITION

   

X

647

Enumerated

   

BIOS_VERSION

   

X

3876

String

   

BOARD_TEMPERATURE

   

X

2580

Real

   

CHECK_IN_INTERVAL

   

X

32561

Unsigned

X

1–3,600

COMPLETION_DOMAINS

   

X

32532

List

   

COMPUTER_NAME

   

X

32531

String

X

max 40 characters

CONTACT_PERSON

   

X

32554

String

X

 

COV_RECEIVE_RATE

   

X

650

Unsigned

   

COV_TRANSMIT_RATE

   

X

651

Unsigned

   

CPU_TEMPERATURE

   

X2

2579

Real

   

CPU_USAGE

   

X

2583

Real

   

DEFAULT_BASE_UNITS

   

X

2203

Enumerated

   

DEVICE_GONE_INTERVAL

   

X

32563

Unsigned

X

0–168

DHCP_ENABLED

   

X

1138

Boolean

X

 

DNS_SERVER_IP_ ADDRESS

   

X

32534

Complex

X

 

DOMAIN_NAME

   

X

2334

String

X

 

EMAIL_ AUTHENTIFICATION_TYPE

   

X

3814

Enumerated

X

 

EMAIL_DDA

   

X

32568

Complex

X

 

EMAIL_DIAGNOSTICS

   

X

3133

String

   

ENABLE_AUDIT_LEVEL

   

X

32549

Unsigned

X

1–4

ENABLED

   

X

673

Boolean

   

ESTIMATED_FLASH_ AVAILABLE

   

X2

2395

Real

   

ESTIMATED_FLASH_ USAGE

   

X

2395

Real

   

EXECUTION_PRIORITY

   

X

2197

Enumerated

   

EXTENDED_PROTO_ VERSION

   

X

2291

Unsigned

   

EXTERNAL_MODEM_ CONFIG

   

X

32530

Complex

X

 

FAIL_EMAIL_ADDRESS

   

X

32542

Complex

X

 

FLASH_USAGE

   

X

2584

Real

   

INCOMING_STATUS

   

X

32567

Enumerated

   

INTERNAL_MODEM_ CONFIG

   

X

32529

Complex

X

 

INTERNODE COMM_TIMER

   

X

845

Unsigned

   

IP_MASK

   

X

1136

Complex

X

 

IP_ROUTER_ADDRESS

   

X

1137

Complex

X

 

ITEM_REFERENCE

   

X

32527

String

   

JCI_IP_ADDRESS

   

X

1135

Complex

X

 

JCI_STATUS

   

X

847

Enumerated

   

LAN_STATUS

   

X

32564

Enumerated

   

LAST_IDLE_SAMPLE

   

X

30082

Real

   

LOCAL_SITE_DIRECTOR

   

X

32557

Complex

X

 

MAX_MESSAGE_BUFFER

   

X

848

Unsigned

X

 

MEMORY_USAGE

   

X

2581

Real

   

NAME

   

X

2390

String

X

max 400 characters

NETWORK_TOLERANCE

   

X

864

Enumerated

X

 

OBJECT_MEMORY_USAGE

   

X

2582

Real

   

OBTAIN_DNS_ADDRESS

   

X

32533

Boolean

X

 

PAGER_DDA

   

X

32569

Complex

X

 

PAGER_DIAGNOSTICS

   

X

30100

String

   

PAGER_DIALUP_CONFIG

   

X

32535

Complex

X

 

PAGER_DIALUP_STATUS

   

X

32565

Enumerated

   

POP_PASSWORD

   

X

32541

String

X

 

POP_SERVER_HOSTNAME

   

X

32539

String

X

 

POP_USER_NAME

   

X

32540

String

X

 

PORT_NUMBER

   

X

1180

Unsigned

X

0–65,535

POWER_CONSECUTIVE_ SAMPLES

   

X

32551

Unsigned

X

1–32

POWER_SAMPLING_ INTERVAL

   

X

32550

Unsigned

   

READ_ONLY_ COMMUNITY

   

X

32555

String

X

 

READ_WRITE_ COMMUNITY

   

X

32556

String

X

 

SERIAL_PORT_CABLE_CONFIGURATION

   

X

32528

Complex

X

 

SET_TIME

   

X

3864

Enumerated

X

 

SMTP_PASSWORD

   

X

3861

String

X

 

SMTP_PORT

   

X

32538

Unsigned

X

0–65,535

SMTP_SERVER_HOST

   

X

32537

Complex

X

 

SMTP_USER_NAME

   

X

3815

String

X

 

SNMP_DDA

   

X

32570

Complex

X

 

SNMP_ENABLED

   

X

32552

Boolean

X

 

SNMP_MANAGEMENT_ DEVICE

   

X

32553

Complex

X

 

SNMP_VERSION

   

X

32622

Enumerated

X

 

STATUS

   

X

512

Enumerated

   

SYNC_TIME

   

X

32616

Boolean

   

TREND_MEMORY_USAGE

   

X2

3646

Real

   

XMS_DIALUP_ CONFIGURATION

   

X2

32563

Complex

X

 

XMS_DIALUP_STATUS

   

X2

32566

Enumerated

   
1 Write does not take effect until after reboot.
2 Not present in all instances.