Table 1. Command Object

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

OBJECT_NAME

X

   

77

 

X

 

PRESENT_VALUE

X

   

85

 

X

 

ACTION_TEXT

 

X

 

3

 

X

60 characters max

DESCRIPTION

 

X

 

28

 

X

64 characters max

ALARM_STATE

   

X

1006

Enumerated

   

AUTHORIZATION_CATEGORY

   

X

908

Enumerated

X

0–249

COMMAND_COUNT

   

X

1545

Unsigned

   

ENABLED

   

X

673

Boolean

X

 

EXECUTION_PRIORITY

   

X

2197

Enumerated

X

0–3

INSTANCE_NUMBER

   

X1

32589

Unsigned

   

ITEM_REFERENCE

   

X

32527

CharacterString

   

REMOTE_DESCRIPTION

   

X1

32519

CharacterString

X

 

REMOTE_DEVICE_ADDR

   

X1

538

Complex

   

REMOTE_OBJECT_NAME

   

X1

2564

CharacterString

   

STATES_TEXT

   

X

931

Enumerated

X2

 

STATES_TEXT_ERROR_STATUS

   

X

64022

Enumerated

   

STATUS

   

X

512

Enumerated

   

USER_NAME

   

X

2390

CharacterString

X

 

USER_SELECTED_STATES_TEXT

   

X

1103

Boolean

X

 
1 Not present in all instances.
2 Not writable in all instances.