Character String Value - Metasys - LIT-12011924 - Supervisory Device - Network Engine - 9.0

NIEx9 Protocol Implementation Conformance Statement

Brand
Metasys
Product name
Network Engine
Document type
Protocol Implementation Conformance Statement
Document number
LIT-12011924
Version
9.0
Language
English

Dynamically Creatable: No

Dynamically Deletable: No

Table 1. Character String Value

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

OBJECT_NAME

X

   

77

 

X

 

PRESENT_VALUE

X

   

85

 

X

 

ACKED_TRANSITIONS

 

X1

 

0

     

ALARM_VALUES

 

X1

  7  

X

 

DESCRIPTION

 

X

 

28

 

X

64 characters max

EVENT_ENABLE

 

X1

 

35

 

X

 

EVENT_MESSAGE_TEXTS

 

X1

  351      

EVENT_STATE

 

X1

 

36

     

EVENT_TIME_STAMPS

 

X1

 

130

     

FAULT_VALUES

 

X2

 

39

 

X

0–65,535

NOTIFICATION_CLASS

 

X1

 

17

 

X

1–4, 194, 303

NOTIFY_TYPE

 

X1

 

72

 

X

 

OUT_OF_SERVICE

 

X

 

81

 

X

 

PRIORITY_ARRAY

 

X2

 

87

     

PROFILE_NAME

 

X

 

168

     

RELIABILITY

 

X

  103  

X

 

RELINQUISH_DEFAULT

 

X2

 

104

 

X

 

TIME_DELAY

 

X1

 

113

 

X

0–65,535

ALARM_MESSAGE_TEXT

   

X1

536

CharacterString

X

 

ALARM_STATE

   

X

1006

Enumerated

   

AUTHORIZATION_CATEGORY

   

X

908

Enumerated

X

0–249

ENABLED

   

X

673

Boolean

X

 

EXECUTION_PRIORITY

   

X

2197

Enumerated

X

0–3

GRAPHIC

   

X1

32581

CharacterString

X

 

GRAPHIC_ALIAS

   

X1

32623

CharacterString

X

 

INSTANCE_NUMBER

   

X

32589

Unsigned

   

INTRINSIC_ALARMING_DEFINED

   

X2

569

Boolean

X

 

ITEM_REFERENCE

   

X

32527

CharacterString

   

REMOTE_DESCRIPTION

   

X2

32519

CharacterString

X

 

REMOTE_DEVICE_ADDR

   

X2

538

Complex

   

REMOTE_OBJECT_NAME

   

X2

2564

CharacterString

   

STATUS

   

X

512

Enumerated

   

STATUS FLAGS

   

X

512

Enumerated

   

USER_NAME

   

X

2390

CharacterString

X

400 characters max

1 Only present when intrinsic alarm is enabled.
2 Not present in all instances.