Averaging - Metasys - LIT-12011924 - Supervisory Device - Network Engine - 9.0

NIEx9 Protocol Implementation Conformance Statement

Brand
Metasys
Product name
Network Engine
Document type
Protocol Implementation Conformance Statement
Document number
LIT-12011924
Version
9.0
Language
English

Dynamically Creatable: No

Dynamically Deletable: No

Table 1. Averaging

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

OBJECT_NAME

X

   

77

 

X

 

WINDOW_INTERVAL

X

   

147

 

X

 

WINDOW_SAMPLES

X

   

148

 

X

 

DESCRIPTION

 

X

 

28

 

X

64 characters max

MIN_VALUE_TIMESTAMP

 

X

 

150

     

MAX_VALUE_TIMESTAMP

 

X

 

149

     

AUTHORIZATION_CATEGORY

   

X

908

Enumerated

X

0–249

ENABLED

   

X

673

Boolean

X

 

EXECUTION_PRIORITY

   

X

2197

Enumerated

X

0–3

INPUT_REFERENCE

   

X

545

Complex

   

ITEM_REFERENCE

   

X

32527

CharacterString

   

REMOTE_DESCRIPTION

   

X1

32519

CharacterString

X

 

REMOTE_DEVICE_ADDR

   

X1

538

Complex

   

REMOTE_OBJECT_NAME

   

X1

2564

CharacterString

   

STATUS

   

X

512

Enumerated

   

USER_NAME

   

X

2390

CharacterString

X

400 characters max

1 Not present in all instances.