Table 1. Accumulator

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

MAX_PRES_VALUE

X

   

65

 

X

 

OBJECT_NAME

X

   

77

 

X

 

OUT_OF_SERVICE

X

   

81

 

X

 

PRESENT_VALUE

X

   

85

 

X

 

SCALE

X

   

187

 

X

 

UNITS

X

   

117

 

X

0–65,535

ACKED_TRANSITIONS

 

X1

 

0

     

DESCRIPTION

 

X

 

28

 

X

64 characters max

DEVICE_TYPE

 

X

 

31

 

X

20 characters max

EVENT_ENABLE

 

X1

 

35

 

X

 

EVENT_MESSAGE_TEXTS

 

X1

  351      

EVENT_TIME_STAMPS

 

X1

 

130

     

HIGH_LIMIT

 

X1

 

45

 

X

 

LIMIT_ENABLE

 

X1

 

52

 

X

 

LIMIT_MONITORING_INTERVAL

 

X1

 

182

 

X

 

LOGGING_OBJECT

 

X2

  183      

LOGGING_ RECORD

 

X2

 

184

     

LOW_LIMIT

 

X1

 

59

 

X

 

NOTIFICATION_CLASS

 

X1

 

17

 

X

1–4, 194,303

NOTIFY_TYPE

 

X1

 

72

 

X

 

PRESCALE

 

X

 

185

 

X

 

PULSE_RATE

 

X1

 

186

 

X

 

RELIABILITY

 

X

 

103

 

X 3

 

TIME_DELAY

 

X1

 

113

 

X

 

VALUE_BEFORE_CHANGE

 

X

  190      

VALUE_CHANGE_TIME

 

X

  192      

VALUE_SET

 

X

  191  

X

0–268,435,455

ALARM_MESSAGE_TEXT

   

X1

536

CharacterString

X

 

ALARM_STATE

   

X

1006

Enumerated

   

ANTI_SPIKE

   

X2

722

Boolean

X

 

AUTHORIZATION_CATEGORY

   

X

908

Enumerated

X

0-249

COV_COUNT

   

X

839

Unsigned

   

DEVICE_MAC_ADDRESS

   

X

3629

Unsigned

   

DISPLAY_ PRECISION

   

X

661

Enumerated

X

 

ENABLED

   

X

673

Boolean

X

 

EXECUTION_PRIORITY

   

X

2197

Enumerated

X

0–3

GRAPHIC

   

X1

32581

CharacterString

X

 

GRAPHIC_ALIAS

   

X1

32623

CharacterString

X

 

IN_TEST

   

X

3368

Boolean

   

INSTANCE_ NUMBER

   

X

32589

Unsigned

   

ITEM_REFERENCE

   

X

32527

CharacterString

   

INTERNAL_UNITS

   

X

3432

Enumerated

X

 

OFFLINE

   

X

913

Boolean

   

PERIODIC_ UPDATE

   

X

2192

Unsigned

X

 

REMOTE_DESCRIPTION

   

X2

32519

CharacterString

X

 

REMOTE_DEVICE_ADDR

   

X2

538

Complex

   

REMOTE_OBJECT_NAME

   

X2

2564

CharacterString

   

ROLLOVER_LIMIT

   

X2

823

Unsigned

X

 

SAB_MAC_ADDR

   

X

3645

Unsigned

   

SCALED_PRESENT_VALUE

   

X

4694

Unsigned

   

SCALED_VALUE

   

X

4694

Real

   

SLOT

   

X

519

Unsigned

   

STATUS

   

X

512

Enumerated

   

TRUNK_NUMBER

   

X

549

Unsigned

   

USER_NAME

   

X

2390

CharacterString

X

400 characters max

1 Only present when intrinsic alarming is enabled.