BACnet Interoperability Building Blocks (BIBBs) (Annex K) - Metasys - LIT-12011924 - Supervisory Device - Network Engine - 9.0

NIEx9 Protocol Implementation Conformance Statement

Brand
Metasys
Product name
Network Engine
Document type
Protocol Implementation Conformance Statement
Document number
LIT-12011924
Version
9.0
Language
English

The following table lists all BIBBs that are supported. The table is divided into BIBBs required for the BACnet Building Controller (B-BC) profile, followed by additional BIBBs that are supported but not required for the B-BC profile.

Table 1. BACnet B-BC BIBBs Supported

BIBB Name (A = Initiates and B = Executes)

Designation

Required for B-BC Profile

Alarm and Event - ACK - B

AE-ACK-B

Alarm and Event - Enrollment Summary - B

AE-ESUM-B

Alarm and Event - Information - B

AE-INFO-B

Alarm and Event - Notification - Internal - B

AE-N-I-B

Device Management - Dynamic Device Binding - A

DM-DDB-A

Device Management - Dynamic Device Binding - B

DM-DDB-B

Device Management - Device Communication Control - B

DM-DCC-B

Device Management - Device Object Binding - B

DM-DOB-B

Device Management - Dynamic Time Synchronization - B

DM-TS-B

Device Management - Dynamic UTC Time Synchronization - B

DM-UTC-B

Device Management - Reinitialize Device - B

DM-RD-B

Device Management - Backup and Restore - B

DM-BR-B

Data Sharing - Read Property - A

DS-RP-A

Data Sharing - Read Property - B

DS-RP-B

Data Sharing - Read Property Multiple - A

DS-RPM-A

Data Sharing - Read Property Multiple - B

DS-RPM-B

Data Sharing - Write Property - A

DS-WP-A

Data Sharing - Write Property - B

DS-WP-B

Data Sharing - Write Property Multiple - B

DS-WPM-B

Scheduling - External - B

SCHED-E-B

Trending - Viewing and Modifying Trends Internal - B

T-VMT-I-B

Trending - Automated Trend Retrieval - B

T-ATR-B

Not Required for B-BC Profile

Alarm and Event - ACK - A

AE-ACK-A

Alarm and Event - Notification

AE-N-A

Alarm and Event - Alarm Summary - B

AE-ASUM-B

Alarm and Event - Information - A

AE-INFO-A

Device Management - Device Object Binding - A

DM-DOB-A

Device Management - Restart - B

DM-R-B

Device Management - List Manipulation - A

DM-LM-A

Device Management - List Manipulation - B

DM-LM-B

Device Management - Object Creation and Deletion - B

DM-OCD-B

Device Management - Time Synchronization - A

DM-TS-A

Device Management - UTC Time Synchronization - A

DM-UTC-A

Data Sharing - COV - A

DS-COV-A

Data Sharing - COV - B

DS-COV-B

Data Sharing - COVP - A

DS-COVP-A

Data Sharing - COVP - B

DS-COVP-B

Data Sharing - COVU - A

DS-COVU-A

Data Sharing - COVU - B

DS-COVU-B

Data Sharing - Write Property Multiple - A

DS-WPM-A

Network Management - Router Configuration - B

NM-RC-B

Scheduling - Internal - B

SCHED-I-B