NIE59 Version 5.2 or Lower - Metasys - LIT-12011919 - MS-MBUSN89-0 - MS-NIE2920-0 - MS-NIE89SW-6 - MS-NIE2966-0 - MS-KNXN89-0 - MS-NIE2910-0 - MS-NIE5920-2 - MS-NIE2960-0 - MS-NIE5960-2 - MS-NIE3910-2 - MS-NIE3920-2 - MS-NIE2916-0 - MS-NIE2926-0 - MS-NIE4920-2 - MS-NIE4910-2 - MS-MODBUSN89-0 - MS-NIE89SW-0 - Bulb controller - NIEx9 Network Integration Engine - 7

NIEx9 Driver Manager Application Note

Product
Network Engines > Network Control Engines > NIEx9 Network Integration Engine
Document number
LIT-12011919
Version
7
Revision date
2017-08-01

To manage the communication drivers and the license file, the NIEx9 Driver Manager uses FTP connectivity. The FTP server is natively present on the NIE29, NIE39 and NIE49, but it is not present on the NIE59 models. To have FTP connectivity that the NIEx9 Driver Manager can use, you must install the FTP server software on the NIE59 using the Remote Desktop connection.