Schedule - Metasys - LIT-1201532 - Supervisory Device - NAE35 Network Automation Engine - NAE45 Network Automation Engine - NAE55 Network Automation Engine - NAE85 Network Automation Engine - NCE25 Network Control Engine - 9

NAE/NCE Protocol Implementation Conformance Statement

Brand
Metasys
Product name
NAE35 Network Automation Engine
NAE45 Network Automation Engine
NAE55 Network Automation Engine
NAE85 Network Automation Engine
NCE25 Network Control Engine
Document type
Protocol Implementation Conformance Statement
Document number
LIT-1201532
Version
9
Revision date
2019-04-09
Language
English

Dynamically Creatable: Yes

Dynamically Deletable: Yes

Table 1. Schedule

Property Name

Required

Optional

Proprietary

Property ID

Data Type

Writable

Range

EFFECTIVE_ PERIOD

X

   

32

 

X

 

OBJECT_ PROPERTY_REF

X

    78  

X

 

OBJECT_NAME

X

   

77

 

X

 

OUT_OF_ SERVICE

X

   

81

 

X

 

PRESENT_ VALUE

X

   

85

 

X1

 

PRIORITY_FOR _WRITING

X

   

88

 

X

 

PROPERTY_ LIST

X

   

371

     

SCHEDULE_ DEFAULT

X

   

174

 

X

 

DESCRIPTION

 

X

 

28

 

X

64 characters max

EXCEPTION_ SCHEDULE

 

X

 

38

 

X

 

WEEKLY_ SCHEDULE

 

X

 

123

 

X

 

ALARM_STATE

   

X

1006

Enumerated

   

AUTHORIZA- TION_ CATEGORY

   

X

908

Enumerated

X

0–249

DEVICE TIME ZONE

   

X

1403

Enumerated

   

ENABLED

   

X

673

Boolean

X

 

EXECUTION_ PRIORITY

   

X

2197

Enumerated

X

0–3

ITEM_ REFERENCE

   

X

32527

Character String

   

JCI_EXCEPTION _SCHEDULE

   

X

2573

List

X

 

JCI_LIST_OF _PROPERTY _REF

   

X

2574

List

X

 

REMOTE_ DESCRIPTION

   

X2

32519

Character String

X

 

REMOTE_ DEVICE_ADDR

   

X2

538

Complex

   

REMOTE_ OBJECT_NAME

   

X2

2564

Character String

   

STATES TEXT

   

X

931

Enumerated

X

 

STATUS

   

X

512

Enumerated

   

USER_NAME

   

X

2390

Character String

X

400 characters max

1 Writable when OUT_OF_SERVICE is true.