Dynamically Creatable: Yes
Dynamically Deletable: Yes
|
Property Name |
Required |
Optional |
Proprietary |
Property ID |
Data Type |
Writable |
Range |
|---|---|---|---|---|---|---|---|
|
ACK_ REQUIRED |
X |
1 |
X |
||||
|
OBJECT_NAME |
X |
77 |
X |
||||
|
PRIORITY |
X |
86 |
X |
||||
|
PROPERTY_ LIST |
X |
371 |
|||||
|
RECIPIENT_ LIST |
X |
102 |
X |
||||
|
DESCRIPTION |
X |
28 |
X |
64 characters max |
|||
|
ALARM_STATE |
X |
1006 |
Enumerated |
||||
|
AUTHORIZA- TION_ CATEGORY |
X |
908 |
Enumerated |
X |
0–249 |
||
|
ENABLED |
X |
673 |
Boolean |
X |
|||
|
EXECUTION_ PRIORITY |
X |
2197 |
Enumerated |
X |
0–3 |
||
|
ITEM_ REFERENCE |
X |
32527 |
Character String |
||||
|
REMOTE_ DESCRIPTION |
X1 |
32519 |
Character String |
X |
|||
|
REMOTE_ DEVICE_ADDR |
X1 |
538 |
Complex |
||||
|
REMOTE_ OBJECT_NAME |
X1 |
2564 |
Character String |
||||
|
STATUS |
X |
512 |
Enumerated |
||||
|
USER_NAME |
X |
2390 |
Character String |
X |
400 characters max |
1 Not
present in all instances.