A single Door object is represented by one Metasys Object:

Metasys object attribute

ID

SUB ID

Possible values description

(R)eadable (W)ritable

Point definition

 

Status

1

0

Normal (0) / Door Forced (1) / Door Held (2)

R

Value

2

1

Door Opened (0) / Door Closed (1)

R

Access Status

3

-1

Access Granted (0) / Access Denied (1) / Normal (2)

R

Access Granted

10

-1

Idle State (0) / Access Granted (1)

R

Access Denied

11

-1

Idle State (0) / Access Denied (1)

R

Command

4

2

Locked (0) / Unlocked (1)

R W