  1. Open the CAF file in CCT.
  2. Locate the SAB port. Connect the Wireless Commissioning Converter (MS-BTCVT-1) to the SAB port. If you are using a Netsensor, the port is on the sensor. If you are reusing an existing sensor, the port is on the Y adapter on the controller.
  3. Using the MS-BTCVT-1, establish a connection to the VMA 1832 controller's SAB port.
  4. Load the application into the controller. Refer to Controller Tool Help (LIT-12011147) for more information about loading the controller.
    Note: If the VMA 1832 controller is downloaded prior to changing the point mappings to the supervisory device, the controller shows up as offline in the supervisory device.