This module is responsible for translating the OCCSCHED command from a supervisory device to the Occupancy Schedule input of the Occupancy Mode Determination. It also allows the OCCTIME to be entered in minutes and then converts it to seconds for Occupancy Mode Determination.
This module is typically placed in the Setpoint Determination column.
You can view and modify the modules in this group's logic.
Table 1 describes the attributes used by the N2 - Occupancy Mode Input module:
| Name | Type | Description | Default Value |
|---|---|---|---|
|
Occ Schedule |
G, V |
The Occupancy Schedule using the Gen 3 Enum Set |
Set Name: Occ Schedule |
| Output | V | The amount of time that temporary occupancy is active in seconds |
Display Units: seconds |
| Occupancy Schedule | The occupancy schedule using the Enum Set for N2-based controllers |
Unoccupied Set Name: Occ Mode 4 States |
|
| Input | The amount of time that temporary occupancy is active in minutes | 6.0 Display Units: minutes |