Additional N1 Network Setup for MVE - Metasys - LIT-1201535 - Supervisory Device - Network Engine

N1 Migration with the NIE Technical Bulletin

Brand
Metasys
Product name
Network Engine
Document type
Technical Bulletin
Document number
LIT-1201535
Revision date
2019-04-09
Language
English
To set up an N1 Network for MVE, perform the steps in N1 Network Setup, and perform these additional steps:
  1. Delete all report router destinations except for transaction reports.
  2. Delete all but one OWS from the global data.
  3. Delete all but one printer (if you need a printer destination for audits).
  4. Delete all objects in NCMs that were added for providing pre-alarm analysis (pseudo or process objects added to report alarms at various delays with escalating priorities).
  5. Deselect the General Alarm Delay setting in Nonvolatile RAM (NOVRAM) for every NCM.