Migrating N1 Features - Metasys - LIT-1201535 - Supervisory Device - N1 Network Engine

N1 Migration with the NIE Technical Bulletin

Product
Document number
LIT-1201535
Revision date
2019-04-09

When one of the objects in Table 1 is added to a database, the N1 Migration server can optionally migrate the following features:

  • Point Configuration

  • Trend Configuration

  • Totalization

  • Point History

  • Alarm Configuration

  • Schedules

  • Calendars

Table 1. Feature Migration Determination

N1 Migration Object Attribute

If Set to True, Results in

Migrate Trend Config

Any trends and point history defined for points in the N1 Network are added as extensions to the corresponding objects in the Metasys system.

Migrate Totalization Config

Any totalizations defined for points in the N1 Network are added as extensions to the corresponding objects in the Metasys system.

Migrate Object Config

If any Metasys N1 Network object is mapped to a Metasys system object, the basic object configuration from the Metasys N1 Network is used to write the basic Metasys system object configuration, such as the description and units. Also, when Migrate Object Config is set to True, any alarms defined for points in the N1 Network are added as extensions to the corresponding objects in the Metasys system.

Migrate Schedules

Any schedules defined for points in the N1 Network are added as described in the Schedule Migration section in this document.