Table 1 through Table 14 contain the command priorities for the NCM and NIE objects. For more information on NCM objects, refer to the appropriate object technical bulletin. For more information on NIE objects, refer to the Object Help section of the Metasys® SMP Help (LIT-1201793) or Metasys® SCT Help (LIT-12011964).

Table 1. Analog Input (N1-AI)

Migration Object Command

NIE Command

NIE Priority

NCM Command

NCM Priority

N1 Feature ID

Out of Service

   

OVERRIDE

N/A

N/A

In Service

   

AUTO

N/A

N/A

Write Attribute of “Present Value”

 

1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16

N/A

N/A

N/A

Release “Present Value”

 

1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16

N/A

N/A

N/A

Table 2. Analog Output (N1-AOD)

Migration Object Command

NIE Command

NIE Priority

NCM Command

NCM Priority

N1 Feature ID

Out of Service

   

N/A

N/A

N/A

In Service

   

N/A

N/A

N/A

Operator Override

 

8

OVERRIDE

1

GATEWAY

Release Operator Override

 

8

AUTO

1

Reverts to previous value

Release “Present Value”

Release

1, 2, 3, 4, 5, 6, 7, 8

AUTO

1

Reverts to previous value

Release “Present Value”

Release

9, 10, 11, 12, 13, 14, 15

RELEASE

2

Reverts to previous value

Release All

   

N/A

N/A

N/A

Adjust

 

16

SET_AOD

2

GATEWAY

Write Attribute of “Present Value”

 

1, 2, 3, 4, 5, 6, 7, 8

OVERRIDE

1

GATEWAY

Write Attribute of “Present Value”

 

9, 10, 11, 12, 13, 14, 15

SET_AOD

2

GATEWAY

Table 3. Analog Output (N1-AOS)

Migration Object Command

NIE Command

NIE Priority

NCM Command

NCM Priority

N1 Feature ID

Out of Service

   

N/A

N/A

N/A

In Service

   

N/A

N/A

N/A

Operator Override

 

8

OVERRIDE

1

GATEWAY

Release Operator Override

 

8

AUTO

1

Reverts to previous value

Release “Present Value”

Release

1, 2, 3, 4, 5, 6, 7, 8

AUTO

1

Reverts to previous value

Release “Present Value”

Release

9, 10, 11, 12

RELEASE

2

Reverts to previous value

Release “Present Value”

Release

13, 14, 15

RELEASE3

3

Reverts to previous value

Release All

   

REL_ALL

3

Reverts to previous value

Adjust

 

16

SET_AOS

3

GATEWAY

Write Attribute of “Present Value”

 

1, 2, 3, 4, 5, 6, 7, 8

OVERRIDE

1

GATEWAY

Write Attribute of “Present Value”

 

9, 10, 11, 12

SET_AOS

2

GATEWAY

Write Attribute of “Present Value”

 

13, 14, 15, 16

SET_AOS

3

GATEWAY

Table 4. Analog Output (N1-AD)

Migration Object Command

NIE Command

NIE Priority

NCM Command

NCM Priority

N1 Feature ID

Out of Service

   

N/A

N/A

N/A

In Service

   

N/A

N/A

N/A

Operator Override

 

8

OVERRIDE

1

GATEWAY

Release Operator Override

 

8

AUTO

1

Reverts to previous value

Release “Present Value”

Release

1, 2, 3, 4, 5, 6, 7, 8

AUTO

1

Reverts to previous value

Release “Present Value”

Release

9, 10, 11, 12

RELEASE

2

Reverts to previous value

Release “Present Value”

Release

13, 14, 15, 16

N/A

N/A

N/A

Release All

   

N/A

N/A

N/A

Adjust

 

16

SET_AD

3

GATEWAY

Write Attribute of “Present Value”

 

1, 2, 3, 4, 5, 6, 7, 8

OVERRIDE

1

GATEWAY

Write Attribute of “Present Value”

 

9, 10, 11, 12

SET_AD

2

GATEWAY

Write Attribute of “Present Value”

 

13, 14, 15, 16

SET_AD

3

GATEWAY

Table 5. Binary Input (N1-B1)

Migration Object Command

NIE Command

NIE Priority

NCM Command

NCM Priority

N1 Feature ID

Out of Service

   

OVERRIDE

N/A

N/A

In Service

   

AUTO

N/A

N/A

Release “Present Value”

 

1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16

N/A

N/A

N/A

Write Attribute of “Present Value”

 

1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16

N/A

N/A

N/A

Table 6. Binary Output (N1-BO)

Migration Object Command

NIE Command

NIE Priority

NCM Command

NCM Priority

N1 Feature ID

Out of Service

   

N/A

N/A

N/A

In Service

   

N/A

N/A

N/A

Operator Override

 

8

OVERRIDE

3

GATEWAY

Release Operator Override

 

8

AUTO

3

Reverts to previous value

Release “Present Value”

Release

1

REL_PRI

1

Reverts to previous value

Release “Present Value”

Release

2

REL_PRI

2

Reverts to previous value

Release “Present Value”

Release

3, 4, 5, 6, 7, 8

AUTO

3

Reverts to previous value

Release “Present Value”

Release

9, 10

REL_PRI

4

Reverts to previous value

Release “Present Value”

Release

11, 12

REL_PRI

5

Reverts to previous value

Release “Present Value”

Release

13

REL_PRI

6

Reverts to previous value

Release “Present Value”

Release

14, 15

REL_PRI

7

Reverts to previous value

Release All

   

REL_ALL

8

N/A

State 0 or State 1

 

16

MAN_STRT or MAN_STOP

8

GATEWAY

Write Attribute of “Present Value”

 

1

START or STOP

1

GATEWAY

Write Attribute of “Present Value”

 

2

START or STOP

2

GATEWAY

Write Attribute of “Present Value”

 

3, 4, 5, 6, 7, 8

OVERRIDE

3

GATEWAY

Write Attribute of “Present Value”

 

9, 10

START or STOP

4

GATEWAY

Write Attribute of “Present Value”

 

11, 12

START or STOP

5

GATEWAY

Write Attribute of “Present Value”

 

13

START or STOP

6

GATEWAY

Write Attribute of “Present Value”

 

14, 15

START or STOP

7

GATEWAY

Write Attribute of “Present Value”

 

16

MAN_STRT or MAN_STOP

8

GATEWAY

Table 7. Binary Output (N1-BD)

Migration Object Command

NIE Command

NIE Priority

NCM Command

NCM Priority

N1 Feature ID

Out of Service

   

N/A

N/A

N/A

In Service

   

N/A

N/A

N/A

Operator Override

 

8

OVERRIDE

1

GATEWAY

Release Operator Override

 

8

AUTO

1

Reverts to previous value

Release “Present Value”

Release

1, 2, 3, 4, 5, 6, 7, 8

AUTO

1

Reverts to previous value

Release “Present Value”

Release

9, 10, 11, 12, 13

RELEASE

2

Reverts to previous value

Release “Present Value”

Release

14, 15, 16

N/A

N/A

N/A

Release All

   

N/A

N/A

N/A

State 1 or State 2

 

16

SET_BD

3

GATEWAY

Write Attribute of “Present Value”

 

1, 2, 3, 4, 5, 6, 7, 8

OVERRIDE

1

GATEWAY

Write Attribute of “Present Value”

 

9, 10, 11, 12, 13

SET_BD

2

GATEWAY

Write Attribute of “Present Value”

 

14, 15, 16

SET_BD

3

GATEWAY

Table 8. Generic Input/Output (N1-CS)

Migration Object Command

NIE Command

NIE Priority

NCM Command

NCM Priority

N1 Feature ID

Operator Override

 

8

OVERRIDE

1

GATEWAY

Release Operator Override

 

8

AUTO

1

Reverts to previous value

Release “Present Value”

Release

1, 2, 3, 4, 5,6, 7, 10, 11, 12, 13, 14, 15

N/A

N/A

N/A

Release “Present Value”

Release

8

AUTO

1

Reverts to previous value

Release “Present Value”

Release

9, 16

Release

3

Reverts to previous value

Release All

   

N/A

N/A

N/A

Adjust/Set state

 

9, 16

STCSMS_CMD

STCSAN_CMD

STCSBN_CMD

3

OPERATOR

Write Attribute of “Present Value”

 

8

OVERRIDE

1

GATEWAY

Write Attribute of “Present Value”

 

1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15

N/A

N/A

N/A

Write Attribute of “Present Value”

9, 16

9, 16

STCSMS_CMD

STCSAN_CMD

STCBN_CMD

3

GATEWAY

Table 9. Multistate Input (N1-MSI)

Migration Object Command

NIE Command

NIE Priority

NCM Command

NCM Priority

N1 Feature ID

Out of Service

   

OVERRIDE

N/A

N/A

In Service

   

AUTO

N/A

N/A

Release “Present Value”

 

1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16

N/A

N/A

N/A

Write Attribute of “Present Value”

 

1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16

N/A

N/A

N/A

Table 10. Multistate Output (N1-MSO)

Migration Object Command

NIE Command

NIE Priority

NCM Command

NCM Priority

N1 Feature ID

Out of Service

   

N/A

N/A

N/A

In Service

   

N/A

N/A

N/A

Operator Override

 

8

OVERRIDE

3

GATEWAY

Release Operator Override

 

8

AUTO

3

Reverts to previous value

Release “Present Value”

Release

1

REL_PRI

1

Reverts to previous value

Release “Present Value”

Release

2

REL_PRI

2

Reverts to previous value

Release “Present Value”

Release

3, 4, 5, 6, 7, 8

AUTO

3

Reverts to previous value

Release “Present Value”

Release

9, 10

REL_PRI

4

Reverts to previous value

Release “Present Value”

Release

11, 12

REL_PRI

5

Reverts to previous value

Release “Present Value”

Release

13

REL_PRI

6

Reverts to previous value

Release “Present Value”

Release

14, 15

REL_PRI

7

Reverts to previous value

Release All

   

REL_ALL

8

N/A

State 0, 1, 2, 3

 

16

SET_MSO

8

GATEWAY

Write Attribute of “Present Value”

 

1

SET_MSO

1

GATEWAY

Write Attribute of “Present Value”

 

2

SET_MSO

2

GATEWAY

Write Attribute of “Present Value”

 

3, 4, 5, 6, 7, 8

OVERRIDE

3

GATEWAY

Write Attribute of “Present Value”

 

9, 10

SET_MSO

4

GATEWAY

Write Attribute of “Present Value”

 

11, 12

SET_MSO

5

GATEWAY

Write Attribute of “Present Value”

 

13

SET_MSO

6

GATEWAY

Write Attribute of “Present Value”

 

14, 15

SET_MSO

7

GATEWAY

Write Attribute of “Present Value”

 

16

SET_MSO

8

GATEWAY

Table 11. Multistate Output (N1-MSD)

Migration Object Command

NIE Command

NIE Priority

NCM Command

NCM Priority

N1 Feature ID

Out of Service

   

N/A

N/A

N/A

In Service

   

N/A

N/A

N/A

Operator Override

 

8

OVERRIDE

1

GATEWAY

Release Operator Override

 

1, 2, 3, 4, 5, 6, 7, 8

AUTO

1

Reverts to previous value

Release “Present Value”

Release

9, 10, 11, 12, 13

RELEASE

2

Reverts to previous value

Release “Present Value”

Release

14, 15, 16

N/A

N/A

N/A

Release All

   

N/A

N/A

N/A

State 0, 1, 2, 3

 

16

SET_MSD

3

GATEWAY

Write Attribute of “Present Value”

 

1, 2, 3, 4, 5, 6, 7, 8

OVERRIDE

1

GATEWAY

Write Attribute of “Present Value”

 

9, 10, 11, 12, 13

SET_MSD

2

GATEWAY

Write Attribute of “Present Value”

 

14, 15, 16

SET_MSD

3

GATEWAY

Table 12. Pulse Counter (N1-ACM)

Migration Object Command

NIE Command

NIE Priority

NCM Command

NCM Priority

N1 Feature ID

Preset Counter

   

N/A

N/A

N/A

Table 13. Multiple Command (N1-MC)

Migration Object Command

NIE Command

NIE Priority

NCM Command

NCM Priority

N1 Feature ID

Out of Service

   

N/A

N/A

N/A

In Service

   

N/A

N/A

N/A

Operator Override

 

8

OVERRIDE

1

GATEWAY

Release Operator Override

 

8

AUTO

1

Reverts to previous value

Release “Present Value”

Release

1, 2, 3, 4, 5, 6, 7, 8

AUTO

1

Reverts to previous value

Release “Present Value”

Release

9, 10, 11, 12, 13, 14, 15, 16

RELEASE

2

N/A

Release All

   

RELEASE

2

N/A

State 0, 1, 2, 3

 

16

SET_MC

3

GATEWAY

Write Attribute of “Present Value”

 

1, 2, 3, 4, 5, 6, 7, 8

OVERRIDE

1

GATEWAY

Write Attribute of “Present Value”

 

9, 10, 11, 12, 13

SET_MC

2

GATEWAY

Write Attribute of “Present Value”

 

14, 15, 16

SET_MC

3

GATEWAY

Table 14. PID Loop (N1-PIDL)

Migration Object Command

NIE Command

NIE Priority

NCM Command

NCM Priority

N1 Feature ID

Out of Service

   

N/A

N/A

N/A

In Service

   

N/A

N/A

N/A

Operator Override

 

8

OVERRIDE

1

GATEWAY

Release Operator Override

 

8

AUTO

1

Reverts to previous value

Release “Setpoint”

Release

1, 2, 3, 4, 5, 6, 7, 8

AUTO

1

Reverts to previous value

Release “Setpoint”

Release

9, 10, 11, 12, 13

RELEASE

2

Reverts to previous value

Release “Setpoint”

Release

14, 15, 16

N/A

N/A

N/A

Release All

   

N/A

N/A

N/A

Adjust

 

16

SET_PIDL

3

GATEWAY

Write Attribute of “Setpoint”

 

1, 2, 3, 4, 5, 6, 7, 8

OVERRIDE

1

GATEWAY

Write Attribute of “Setpoint”

 

9, 10, 11, 12, 13

SET_PIDL

2

GATEWAY

Write Attribute of “Setpoint”

 

14, 15, 16

SET_PIDL

3

GATEWAY

Note: Refer to the PID Loop Objects Technical Bulletin (Order No. 636-100) for information on implementing the Value attribute of the PIDL object.