Point comparison - Metasys - LIT-12012005 - Field Device - N2 Controller - 13.0

Modernization Guide for N2 Controllers - Metasys

Brand
Metasys
Product name
N2 Controller
Document type
User Guide
Document number
LIT-12012005
Version
13.0
Revision date
2023-10-16
Language
English
Table 1. XTM point type count comparison

Code Number

Termination Type

Analog Inputs (AI)

Binary Input (BI)

Analog Output (AO)

Binary Output (BO)

Relay Output (RO)

Expansion modules used with XTM-105 communications interface:

XPA-821

Spade Lug

6

2

XPB-821

8

XPL-401

4

3 single stage

XPL-402

4

1 single stage

1 two stage

XPL-403

4

1 three stage

XPE-401

4

3 single stage

XPE-402

4

1 single stage

1-two stage

XPE-403

4

1 three stage

XPE-404

4

4

XPT-401

4

4

XPT-861

 

8

Table 2. CGM/FAC/IOM point type comparison
Code number Termination type UI BI AO BO CO UO RO
CGM04060

Screw Terminals

3 1 - 2 4 - -
CGM09090 7 2 2 3 4 - -
FAC2611 6 2 2 3 4 - -
FAC2612 5 4 - - 4 - 5
FAC3613 8 6 6 6 - - -
IOM1711 - 4 - - - - -
IOM2711 2 - - - - 2 2
IOM2721 8 - 2 - - - -
IOM3711 4 - - - - 4 4
IOM3721 - 16 - - - - -
IOM3731 - 8 - 8 - - -
IOM4711 6 2 2 3 4 - -