Legacy VAV1xx controllers identify themselves to their N2 supervisor as a VAV device type. The CVM, VMA and FEC support identifying themselves to its N2 supervisor as a VAV device type, which eliminates the need to change this in the N2 supervisor's configuration. To configure this capability, use the N2 Mapping feature of CCT to set the CVM, VMA or FEC controller's device type to VAV as shown in the following figure.

Figure 1. Using CCT to set the FEC Controller's device type to VAV

No utilities are available to automatically recreate the N2 Mapping Table, so you must manually recreate it using CCT.